Belden Store
21598

Product Number: 21598

TC-CIC 600V, 50+G C #12 AWG BC, XLPE Ins, Blk PVC Jkt, 90C Dry/Wet CSA HL SUN RES DIR BUR

Canadian Instrumentation Cable TC-CIC 600V, 50+G Conductor 12AWG (7x20) Bare Copper, XLPE Insulation, Black PVC Outer Jacket, CSA 22.2 #239 (CIC) CSA 22.2 #230 (TC) SUN RES

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Suitable ApplicationsCEC Power and Control Applications

Construction Details

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Conductor(s)50127x20BC - Bare Copper
Ground Wire114 AWG7x22BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)XLP, XLPO, XLPE (Thermoset)0.032 in (0.81 mm)0.150 in (3.81 mm)Black and numbered
Ground WireXLP, XLPO, XLPE (Thermoset)0.150 in (3.81 mm)Green

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.095 in (2.4 mm)
Nom. Diameter1.452 in (36.88 mm)
RipcordYes

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)1.6 Ohm/1000ft (5.2 Ohm/km)25 Amps per Conductor at 30oC
Ground Wire

Voltage

Voltage Rating(CSA TC)

Mechanical Characteristics

Bulk Cable Weight1645 lbs/1000ft (2448 kg/km)

Temperature

OperatingWet/Dry: -40°C to 90°C
Installation-25°C To +90

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
AWM ComplianceC22.2#230 Type TC, C22.2#239 Type CIC
CEC / C(UL) ComplianceTC, CIC.
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.19 Revision Date: 05-21-2026

Resources

Related tray & tc cable