Belden Store
21550

Product Number: 21550

TC-CIC 600V, 2+G C #12 AWG BC, XLPE Ins, Blk PVC Jkt, 90C Dry/Wet CSA HL SUN RES DIR BUR

Two 12 AWG stranded (7x20) bare copper conductors plus ground wire, cross-linked polyethylene insulation, PVC jacket.

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Suitable ApplicationsCEC Power and Control Applications

Construction Details

Overall Cable Diameter (Nominal)0.421 in

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Conductor(s)212 AWG7x20BC - Bare Copper
Ground Wire114 AWG7x22BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)XLP, XLPO, XLPE (Thermoset)0.032 in (0.81 mm)0.150 in (3.81 mm)Black, White
Ground WireXLP, XLPO, XLPE (Thermoset)0.030 in (0.76 mm)0.150 in (3.81 mm)Green

Outer Shield

MaterialNo Shield

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.057 in (1.4 mm)
Nom. Diameter0.421 in
RipcordYes

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)1.6 Ohm/1000ft (5.2 Ohm/km)30 Amps per Conductor at 30oC
Ground Wire

Voltage

Voltage Rating600 V (CSA TC)

Mechanical Characteristics

Max. Pull Tension228 lbs (103 kg)
Bulk Cable Weight111 lbs/1000ft (165 kg/km)

Temperature

UL Temperature90°C Dry, 90°C Wet
OperatingWet/Dry: -40°C to 90°C
Installation-25°C To +90

Bend Radius

Stationary Min.1.684 in (42.77 mm)
Installation Min.2.105 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance, Burial
Flammability / Reaction to FireFT4
AWM ComplianceC22.2#230 Type TC, C22.2#239 Type CIC
CEC / C(UL) ComplianceTC, CIC.
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.176 Revision Date: 05-20-2026

Resources

Related tray & tc cable