TC- RW90 1000V, 4+G C #2 Str BC, XLPE Ins, Blk PVC Jkt, 90C Dry/Wet CSA HL SUN RES DIR BUR
CSA Tray TC- RW90 1000V, 4+G Conductor 2 AWG (7x10) Bare Copper, XLPE Insulation, Black PVC Outer Jacket, 90C Dry/Wet CSA HL SUN RES DIR BUR
- Availability
- Global
- Status
- Active
Specifications
Product Overview
| Suitable Applications | CEC Power and Control Applications |
|---|
Construction Details
Conductor
| Element | No. of Elements | Size | Stranding | Material |
|---|---|---|---|---|
| Conductor(s) | 4 | 2 AWG | 7x10 | BC - Bare Copper |
| Ground Wire | 1 | 6 AWG | 7x14 | BC - Bare Copper |
Insulation
| Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|---|---|---|---|
| Conductor(s) | XLP, XLPO, XLPE (Thermoset) | 0.062 in (1.6 mm) | 0.407 in (10.3 mm) | Black , White, Red, Blue |
| Ground Wire | XLP, XLPO, XLPE (Thermoset) | 0.407 in (10.3 mm) | Green |
Outer Shield
| Material | No Shield |
|---|
Outer Jacket
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nom. Thickness | 0.096 in (2.4 mm) |
| Nom. Diameter | 1.149 in (29.18 mm) |
Electrical Characteristics
Electricals
| Element | Nom. Conductor DCR | Max. Current |
|---|---|---|
| Conductor(s) | 0.16 Ohm/1000ft (0.52 Ohm/km) | 130 Amps per Conductor at 30oC |
| Ground Wire |
Voltage
| UL Voltage Rating | 1000 V |
|---|---|
| Voltage Rating | 1000 V (CSA TC) |
Mechanical Characteristics
| Max. Pull Tension | 3088 lbs (1401 kg) |
|---|---|
| Bulk Cable Weight | 1263 lbs/1000ft (1880 kg/km) |
Temperature
| UL Temperature | 90°C Dry, 90°C Wet |
|---|---|
| Operating | Wet/Dry: -25°C to 90°C |
| Installation | -25°C To +90 |
Bend Radius
| Stationary Min. | 13.788 in (350.22 mm) |
|---|---|
| Installation Min. | 13.788 in (350.22 mm) |
Standards and Compliance
| Environmental Suitability | Indoor/Outdoor Direct Burial, Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial |
|---|---|
| Flammability / Reaction to Fire | UL1685 UL Loading, FT4 |
| NEC / UL Compliance | Article 336, TC |
| AWM Compliance | C22.2 #230 Type TC |
| CEC / C(UL) Compliance | 1000V Type RW90 TC, CSA TC. |
| European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2012/19/EU (WEEE) |
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
History
| Update and Revision | Revision Number: 0.49 Revision Date: 05-21-2026 |
|---|
Resources
Related tray & tc cable

1037A
Inst, 3 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
3 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1038A
Inst, 50 Pr #18 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC 150V NPLF 90C Dry 75C Wet
50 · 18 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1039A
Inst, 4 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
4 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1040A
Inst, 6 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
6 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon