TC- RW90 1000V, 3+G C #12 Str BC, XLPE Ins, Blk PVC Jkt, 90C Dry/Wet CSA HL SUN RES DIR BUR
CSA Tray TC- RW90 1000V, 3+G Conductor 12AWG (7x20) Bare Copper, XLPE Insulation, Black PVC Outer Jacket, 90C Dry/Wet CSA HL SUN RES DIR BUR
- Availability
- Global
- Status
- Active
- Orderable items
- 2
Part numbers
21351 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.
| Item # | Putup Type | Order |
|---|---|---|
| 21351 0102500 | Reel | Order online |
| 21351 0105000 | Reel | Order online |
Specifications
Product Overview
| Suitable Applications | CEC Power and Control Applications |
|---|
Construction Details
| Overall Cable Diameter (Nominal) | 0.538 in (13.7 mm) |
|---|
Conductor
| Element | No. of Elements | Size | Stranding | Material |
|---|---|---|---|---|
| Conductor(s) | 3 | 12 AWG | 7x20 | BC - Bare Copper |
| Ground Wire | 1 | 14 AWG | 7x22 | BC - Bare Copper |
Insulation
| Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|---|---|---|---|
| Conductor(s) | XLP, XLPO, XLPE (Thermoset) | 0.0450 in (1.14 mm) | 0.180 in (4.57 mm) | Black, Red, Blue |
| Ground Wire | XLP, XLPO, XLPE (Thermoset) | 0.0450 in (1.14 mm) | 0.163 in (4.14 mm) | Green |
Outer Shield
| Shield Type | Tape |
|---|---|
| Material | Polypropylene Foam |
| Coverage | 100% |
Outer Jacket
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nom. Thickness | 0.057 in (1.4 mm) |
| Nom. Diameter | 0.517 in (13.1 mm) |
| Ripcord | Yes |
Electrical Characteristics
Electricals
| Element | Nom. Conductor DCR | Max. Current |
|---|---|---|
| Conductor(s) | 1.6 ohms/1000 FT | 30 Amps per Conductor at 30oC |
| Ground Wire | 2.68 Ohm/1000ft (8.79 Ohm/km) |
Voltage
| Voltage Rating | 1000 V (CSA TC) |
|---|
Mechanical Characteristics
| Max. Pull Tension | 315 lbs (143 kg) |
|---|---|
| Bulk Cable Weight | 161 lbs/1000ft (240 kg/km) |
Temperature
| Operating | Wet/Dry: -40°C to 90°C |
|---|---|
| Installation | -25°C To +90 |
Bend Radius
| Stationary Min. | 6.45 in (164 mm) |
|---|---|
| Installation Min. | 6.45 in (164 mm) |
Standards and Compliance
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, UV Resistance, Burial |
|---|---|
| CEC / C(UL) Compliance | 1000V Type RW90 TC, TC, C22.2 #230, #38, #0.3 Clause 4.3, LL7874, RW90. |
| European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
History
| Update and Revision | Revision Number: 0.63 Revision Date: 03-31-2026 |
|---|
Resources
Related tray & tc cable

1037A
Inst, 3 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
3 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1038A
Inst, 50 Pr #18 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC 150V NPLF 90C Dry 75C Wet
50 · 18 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1039A
Inst, 4 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
4 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon

1040A
Inst, 6 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet
6 · 16 AWG · BC - Bare Copper · PVC/Nylon - Polyvinyl Chloride + Nylon