Belden Store
1048A

Product Number: 1048A

Inst, 2 Pr #18 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry/Wet

UL Instrumentation, 2 Pair 18AWG (7x26) Bare Copper, PVC-NYL Insulation E1 Color Code, Individual & Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC-ER 150V NPLF 90C Dry/Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

1048A is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorPutup TypeLengthUPCFootnoteOrder
1048A 0107500BlackReel7,500 ft612825105343C ZOrder online

Specifications

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners

Construction Details

Overall Cable Diameter (Nominal)0.379 in (9.63 mm)

Conductor

ElementPair(s)
No. of Elements2
Size18 AWG
Stranding7x26
MaterialBC - Bare Copper

Insulation

ElementPair(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.022 in (0.56 mm)
Nom. Insulation Diameter0.088 in (2.2 mm)
Color CodeICEA Chart E1

Inner Shield

ElementPair(s)
Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type20 AWG (7x28) TC
Noteseach pair, extra polyester tape for isolation

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type18 AWG (7x26) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.379 in (9.63 mm)
RipcordYes

Electrical Characteristics

Nom Outer Shield DCR4.91 Ohm/1000ft (16.1 Ohm/km)

Electricals

ElementPair(s)
Nom. Conductor DCR6.66 Ohm/1000ft
Nom. Inner Shield DCR8.48 Ohm/1000ft (27.8 Ohm/km)
Max. Current11 Amps per conductor @ 30°C

Voltage

UL Voltage Rating600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension125 lbs (56.7 kg)
Bulk Cable Weight74 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
Operating-30°C to 90°C Dry/Wet

Bend Radius

Stationary Min.4.5 in (110 mm)
Installation Min.4.5 in (110 mm)

Standards and Compliance

Environmental SuitabilityIndoor/Outdoor, Indoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL 1685 FT4 Loading, FT4, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, Article 760, NPLF, TC-ER
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.622 Revision Date: 04-10-2026
FootnoteC - CRATE REEL PUT-UP., Z - FINAL PUT-UP MAY VARY (= OR -) 10% FOR SPOOLS OR REELS AND (+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.

Resources

Related tray & tc cable