Belden Store
1044A

Product Number: 1044A

Inst, 20 Pr #16 Str BC, PVC-NYL Ins E1, IS/OS, Blk PVC Jkt, 600V TC-ER 150V NPLF 90C Dry 75C Wet

UL Instrumentation, 20 Pair 16AWG (7x24) Bare Copper, PVC-NYL Insulation E1 Color Code, Individual & Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC-ER 150V NPLF 90C Dry 75C Wet SUN RES DIR BUR

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

1044A is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorPutup TypeLengthUPCFootnoteOrder
1044A 0102500BlackReel2,500 ft612825105299C ZOrder online

Specifications

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners

Construction Details

Overall Cable Diameter (Nominal)1.121 in (28.47 mm)

Conductor

ElementPair(s)
No. of Elements20
Size16 AWG
Stranding7x24
MaterialBC - Bare Copper

Insulation

ElementPair(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.022 in (0.56 mm)
Nom. Insulation Diameter0.101 in (2.57 mm)
Color CodeBlack, White and Numbered

Inner Shield

ElementPair(s)
Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type18 AWG (7x26) TC

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type16 AWG (7x24) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.084 in (2.1 mm)
Nom. Diameter1.121 in (28.47 mm)
RipcordYes

Electrical Characteristics

Nom Outer Shield DCR2.69 Ohm/1000ft (8.83 Ohm/km)

Electricals

ElementPair(s)
Nom. Conductor DCR3.67 Ohm/1000ft (12.0 Ohm/km)

Voltage

UL Voltage Rating600 V (TC-ER), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension1912 lbs (867.3 kg)
Bulk Cable Weight743.4 lbs/1000ft

Temperature

UL Temperature90°C Dry, 75°C Wet
Operating-30C to 90C Dry, 75C wet

Bend Radius

Stationary Min.13.5 in (343 mm)
Installation Min.13.5 in (343 mm)

Standards and Compliance

Environmental SuitabilityIndoor/Outdoor, Indoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL1685 (FT4 Loading), FT4, 1202
NEC / UL ComplianceArticle 336, Article 760, NPLF, TC-ER
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.575 Revision Date: 09-07-2025
FootnoteC - CRATE REEL PUT-UP., Z - FINAL PUT-UP MAY VARY (= OR -) 10% FOR SPOOLS OR REELS AND (+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.