Belden Store
6220UL

Product Number: 6220UL

Fire Alarm, #16-2c BC, FPLP

Fire Alarm Cable, Plenum-FPLP, 2-16 AWG solid bare copper conductors with Flamarrest® insulation, Flamarrest® jacket with ripcord

Availability
Global
Status
Active
Orderable items
11

Ships from and sold by A5 IT.

Part numbers

6220UL is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorUPCOrder
6220UL D15U1000Blue612825174370Order online
6220UL 001U1000Brown—Order online
6220UL 003C500Orange612825174417Order online
6220UL 003U1000Orange612825174424Order online
6220UL 0021000Red612825174394Order online
6220UL 002500Red612825174400Order online
6220UL 002C500Red—Order online
6220UL 002U1000Red612825174387Order online
6220UL 007U1000Violet612825174455Order online
6220UL 004C500Yellow612825174431Order online
6220UL 004U1000Yellow612825174448Order online

Specifications

Product Overview

Suitable ApplicationsFire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification

Construction Details

Overall Cable Diameter (Nominal)0.166 in (4.22 mm)

Conductor

ElementConductor(s)
No. of Elements2
Size16 AWG
StrandingSolid
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.008 in (0.20 mm)
Nom. Insulation Diameter0.067 in (1.7 mm)
Color CodeBlack, Red

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.015 in (0.38 mm)
Nom. Diameter0.166 in (4.22 mm)
RipcordYes

Electrical Characteristics

Electricals

ElementConductor(s)
Nom. Conductor DCR3.85 Ohm/1000ft (12.6 Ohm/km)
Nom. Capacitance Cond-to-Cond37 pF/ft (120 pF/m)
Nom. Inductance0.15 μH/ft (0.49 μH/m)
Max. Current14.4 Amps per conductor @ 25°C

Voltage

UL Voltage Rating300 V

Mechanical Characteristics

Max. Pull Tension62 lbs (28 kg)
Bulk Cable Weight22 lbs/1000ft (33 kg/km)

Temperature

UL Temperature75°C
Operating0°C to +75°C

Bend Radius

Stationary Min.1.32 in (33.5 mm)
Installation Min.1.32 in (33.5 mm)

Standards and Compliance

Environmental SuitabilityIndoor - Plenum, Indoor
Flammability / Reaction to FireNFPA 262, UL 910 (Plenum)
NEC / UL ComplianceArticle 760, FPLP
CEC / C(UL) ComplianceFT6.
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)
Other Standard Compliance(s)California State Fire Marshall
Non-Plenum Number5220UL

History

Update and RevisionRevision Number: 0.580 Revision Date: 03-03-2026
FootnoteC - CRATE REEL PUT-UP.

Resources