Belden Store
26120UL

Product Number: 26120UL

Armored Fire Alarm, #14-2c BC, FPLP

Fire Alarm Cable, Armored Plenum-FPLP, 2-14 AWG solid bare copper conductors with Flamarrest® insulation, Flamarrest® jacket with ripcord

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Suitable ApplicationsFire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification

Construction Details

Outer Jacket1 Table NotesInterlocking Armoring OD: .425 in
Overall Cable Diameter (Nominal).425 in (10.8 mm)

Conductor

ElementConductor(s)
No. of Elements2
Size14 AWG
StrandingSolid
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialPVC - Polyvinyl Chloride
Nom. Thickness.010 in (0.25 mm)
Nom. Insulation Diameter.0845 in (2.15 mm)
Color CodeBlack, Red

Armor

Armor Type & MaterialAIA - Aluminum Interlock Armor
Armor Thickness.425 in (10.8 mm)

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness.015 in (0.38 mm)
Nom. Diameter.201 in (5.11 mm)
RipcordYes
NotesInterlocking Armoring OD: .425 in

Electrical Characteristics

Electricals

ElementConductor(s)
Nom. Conductor DCR2.42 Ohm/1000ft (7.94 Ohm/km)
Max. Current25 Amps per conductor @ 25°C

Voltage

UL Voltage Rating300 V (300 V), 300 V

Mechanical Characteristics

Max. Pull Tension105 lbs (47.6 kg)

Temperature

UL Temperature75°C
Operating0°C to +75°C

Bend Radius

Stationary Min.4.5 in (110 mm)
Installation Min.4.5 in (110 mm)

Standards and Compliance

Environmental SuitabilityIndoor - Plenum, Indoor
Flammability / Reaction to FireNFPA 262, UL 910 (Plenum)
NEC / UL ComplianceArticle 760, FPLP
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)
Other Standard Compliance(s)California State Fire Marshall

History

Update and RevisionRevision Number: 0.21 Revision Date: 03-04-2025

Resources

Related fire alarm cable