Belden Store
26220FL

Product Number: 26220FL

Armored Fire Alarm, #16-2c BC, Shielded, FPLP

Armored Fire Alarm Cable, Plenum-FPLP, 2-16 AWG solid bare copper conductors with Flamarrest® insulation, overall Beldfoil® shield, Flamarrest® jacket with ripcord

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Suitable ApplicationsFire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification, Noisy Environment

Construction Details

Outer Jacket1 Table NotesInterlocking Aluminum Armor OD: .389 in
Overall Cable Diameter (Nominal).389 in (9.88 mm)

Conductor

ElementConductor(s)
No. of Elements2
Size16 AWG
StrandingSolid
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialPVC - Polyvinyl Chloride
Nom. Thickness.010 in (0.25 mm)
Nom. Insulation Diameter.071 in (1.8 mm)
Color CodeBlack, Red

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type24 AWG (19x36) TC

Armor

Armor Type & MaterialAIA - Aluminum Interlock Armor
Armor Material Diameter.389 in (9.88 mm)

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness.015 in (0.38 mm)
Nom. Diameter.178 in (4.52 mm)
RipcordYes
NotesInterlocking Aluminum Armor OD: .389 in

Electrical Characteristics

Electricals

ElementConductor(s)
Nom. Conductor DCR3.85 Ohm/1000ft (12.6 Ohm/km)
Nom. Capacitance Cond-to-Cond77 pF/ft (250 pF/m)
Nom. Capacitance Cond-to-Other (Conds + Shield)139 pF/ft (456 pF/m)
Max. Current14.4 Amps per conductor @ 25°C

Voltage

UL Voltage Rating300 V (300 V)

Mechanical Characteristics

Max. Pull Tension77 lbs (35 kg)

Temperature

UL Temperature75°C
Operating0°C to +75°C

Bend Radius

Stationary Min.4.5 in (110 mm)
Installation Min.4.5 in (110 mm)

Standards and Compliance

Environmental SuitabilityIndoor - Plenum
Flammability / Reaction to FireNFPA 262, UL 910 (Plenum)
CPR ComplianceCPR Euroclass: Eca
NEC / UL ComplianceArticle 760, FPLP
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
UK Regulation ComplianceUKCA Mark
APAC ComplianceChina RoHS II (GB/T 26572-2011)
Other Standard Compliance(s)California State Fire Marshall

History

Update and RevisionRevision Number: 0.8 Revision Date: 02-14-2025