Armored Fire Alarm, #16-2c BC, Shielded, FPLP
Armored Fire Alarm Cable, Plenum-FPLP, 2-16 AWG solid bare copper conductors with Flamarrest® insulation, overall Beldfoil® shield, Flamarrest® jacket with ripcord
- Availability
- Global
- Status
- Active
Specifications
Product Overview
| Suitable Applications | Fire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification, Noisy Environment |
|---|
Construction Details
| Outer Jacket1 Table Notes | Interlocking Aluminum Armor OD: .389 in |
|---|---|
| Overall Cable Diameter (Nominal) | .389 in (9.88 mm) |
Conductor
| Element | Conductor(s) |
|---|---|
| No. of Elements | 2 |
| Size | 16 AWG |
| Stranding | Solid |
| Material | BC - Bare Copper |
Insulation
| Element | Conductor(s) |
|---|---|
| Material | PVC - Polyvinyl Chloride |
| Nom. Thickness | .010 in (0.25 mm) |
| Nom. Insulation Diameter | .071 in (1.8 mm) |
| Color Code | Black, Red |
Outer Shield
| Shield Type | Tape |
|---|---|
| Material | Bi-Laminate (Alum+Poly) |
| Coverage | 100% |
| Drainwire Type | 24 AWG (19x36) TC |
Armor
| Armor Type & Material | AIA - Aluminum Interlock Armor |
|---|---|
| Armor Material Diameter | .389 in (9.88 mm) |
Outer Jacket
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nom. Thickness | .015 in (0.38 mm) |
| Nom. Diameter | .178 in (4.52 mm) |
| Ripcord | Yes |
| Notes | Interlocking Aluminum Armor OD: .389 in |
Electrical Characteristics
Electricals
| Element | Conductor(s) |
|---|---|
| Nom. Conductor DCR | 3.85 Ohm/1000ft (12.6 Ohm/km) |
| Nom. Capacitance Cond-to-Cond | 77 pF/ft (250 pF/m) |
| Nom. Capacitance Cond-to-Other (Conds + Shield) | 139 pF/ft (456 pF/m) |
| Max. Current | 14.4 Amps per conductor @ 25°C |
Voltage
| UL Voltage Rating | 300 V (300 V) |
|---|
Mechanical Characteristics
| Max. Pull Tension | 77 lbs (35 kg) |
|---|
Temperature
| UL Temperature | 75°C |
|---|---|
| Operating | 0°C to +75°C |
Bend Radius
| Stationary Min. | 4.5 in (110 mm) |
|---|---|
| Installation Min. | 4.5 in (110 mm) |
Standards and Compliance
| Environmental Suitability | Indoor - Plenum |
|---|---|
| Flammability / Reaction to Fire | NFPA 262, UL 910 (Plenum) |
| CPR Compliance | CPR Euroclass: Eca |
| NEC / UL Compliance | Article 760, FPLP |
| European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| UK Regulation Compliance | UKCA Mark |
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
| Other Standard Compliance(s) | California State Fire Marshall |
History
| Update and Revision | Revision Number: 0.8 Revision Date: 02-14-2025 |
|---|
Resources
Belden 26220FL technical datasheetSafe-T-Line Product BulletinFire Alarm Cable Product BulletinArmored Power-Limited Fire Alarm FPLPSound, Security & Alarm Cable Selection OverviewAccess Control Composite CablesNewGen Cables Product BulletinBelden Low Capacitance Digital Fire Alarm CablesWaterdog Cables Product BulletinDate: 2005-04-01
Related fire alarm cable

26120UL
Armored Fire Alarm, #14-2c BC, FPLP
2 · 14 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride

26220UL
Armored Fire Alarm, #16-2c BC, FPLP
2 · 16 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride

26320FL
Armored Fire Alarm, #18-2c BC, Shielded, FPLP
2 · 18 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride

26320UL
Fire Alarm, #18-2c BC, FPLP, Armored
2 · 18 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride