Belden Store
6200FL

Product Number: 6200FL

Fire Alarm, #16-2c BC, Shielded, FPLP

Fire Alarm Cable, Plenum-FPLP, 2-16 AWG stranded bare copper conductors with Flamarrest® insulation, overall Beldfoil® shield, Flamarrest® jacket with ripcord

Availability
Americas
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

6200FL is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorUPCOrder
6200FL 0021000Red612825173960Order online
6200FL 002U1000Red612825173953Order online

Specifications

Product Overview

Suitable ApplicationsFire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification, Noisy Environment

Construction Details

Overall Cable Diameter (Nominal)0.184 in

Conductor

ElementConductor(s)
No. of Elements2
Size16 AWG
Stranding19x29
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.009 in (0.23 mm)
Nom. Insulation Diameter0.075 in (1.9 mm)
Color CodeBlack, Red

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type24 AWG (7x32) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.015 in (0.38 mm)
Nom. Diameter0.184 in
RipcordYes

Electrical Characteristics

Nom Outer Shield DCR17.4 Ohm/1000ft (57.1 Ohm/km)

Electricals

Nom. Conductor DCR4.35 Ohm/1000ft
Nom. Capacitance Cond-to-Cond45 pF/ft (150 pF/m)
Nom. Capacitance Cond-to-Other (Conds + Shield)81 pF/ft (270 pF/m)
Max. Current6 Amps per Conductor at 25oC

Voltage

UL Voltage Rating300 V

Mechanical Characteristics

Max. Pull Tension85 lbs (39 kg)
Bulk Cable Weight26 lbs/1000ft

Temperature

UL Temperature75°C
Operating0°C To +75°C

Bend Radius

Stationary Min.2.76 in (70.1 mm)
Installation Min.2.76 in

Standards and Compliance

Environmental SuitabilityIndoor
Flammability / Reaction to FireNFPA 262 (UL910)
NEC / UL ComplianceArticle 760, FPLP
European Directive ComplianceEU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)
Non-Plenum Number5200FL

History

Update and RevisionRevision Number: 0.322 Revision Date: 09-07-2025

Resources

Related fire alarm cable