Belden Store
6120UL

Product Number: 6120UL

Fire Alarm, #14-2c BC, FPLP

Fire Alarm Cable, Plenum-FPLP, 2-14 AWG solid bare copper conductors with Flamarrest® insulation, Flamarrest® jacket with ripcord

Availability
Global
Status
Active
Orderable items
11

Ships from and sold by A5 IT.

Part numbers

6120UL is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorUPCOrder
6120UL 0101000Black612825173731Order online
6120UL D151000Blue612825173700Order online
6120UL 0011000Brown612825173717Order online
6120UL 0051000Green612825350354Order online
6120UL 8771000Natural612825350385Order online
6120UL 0031000Orange612825350347Order online
6120UL 0021000Red612825339564Order online
6120UL 002500Red612825173724Order online
6120UL 0071000Violet612825350361Order online
6120UL 0071000Violet612825350361Order online
6120UL 0041000Yellow612825352228Order online

Specifications

Product Overview

Suitable ApplicationsFire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification

Construction Details

Overall Cable Diameter (Nominal)0.201 in (5.11 mm)

Conductor

ElementConductor(s)
No. of Elements2
Size14 AWG
StrandingSolid
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.010 in (0.25 mm)
Nom. Insulation Diameter0.0845 in (2.15 mm)
Color CodeBlack, Red

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.015 in (0.38 mm)
Nom. Diameter0.201 in (5.11 mm)
RipcordYes

Electrical Characteristics

Electricals

ElementConductor(s)
Nom. Conductor DCR2.42 Ohm/1000ft
Nom. Capacitance Cond-to-Cond37 pF/ft (120 pF/m)
Max. Current25 Amps per conductor @ 25°C

Voltage

UL Voltage Rating300 V

Mechanical Characteristics

Max. Pull Tension99.4 lbs (45.1 kg)
Bulk Cable Weight34 lbs/1000ft

Temperature

UL Temperature75°C
Operating0°C to +75°C

Bend Radius

Stationary Min.1.6 in (41 mm)
Installation Min.1.6 in (41 mm)

Standards and Compliance

Environmental SuitabilityIndoor - Plenum, Indoor
Flammability / Reaction to FireNFPA 262, UL 910 (Plenum)
NEC / UL ComplianceArticle 760, FPLP
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)
Other Standard Compliance(s)California State Fire Marshall
Non-Plenum Number5120UL

History

Update and RevisionRevision Number: 0.440 Revision Date: 09-07-2025
FootnoteC - CRATE REEL PUT-UP.