Fire Alarm, #14-2c BC, FPLP
Fire Alarm Cable, Plenum-FPLP, 2-14 AWG stranded bare copper conductors with Flamarrest® insulation, Flamarrest® jacket with ripcord
- Availability
- Americas
- Status
- Active
- Orderable items
- 2
Part numbers
6100UL is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.
| Item # | Color | UPC | Footnote | Order |
|---|---|---|---|---|
| 6100UL 0021000 | Red | 612825173496 | C | Order online |
| 6100UL 002U1000 | Red | 612825173489 | — | Order online |
Specifications
Product Overview
| Suitable Applications | Fire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification |
|---|
Construction Details
Conductor
| Element | Conductor(s) |
|---|---|
| No. of Elements | 2 |
| Size | 14 |
| Stranding | 19x26 |
| Material | BC - Bare Copper |
Insulation
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nom. Thickness | 0.012 in (0.30 mm) |
| Nom. Insulation Diameter | 0.094 in (2.4 mm) |
| Color Code | Black, Red |
Outer Jacket
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nom. Thickness | 0.015 in (0.38 mm) |
| Nom. Diameter | 0.214 in |
| Ripcord | Yes |
Electrical Characteristics
Electricals
| Nom. Conductor DCR | 2.67 Ohm/1000ft |
|---|---|
| Nom. Capacitance Cond-to-Cond | 32 pF/ft (100 pF/m) |
| Max. Current | 25 Amps per Conductor at 25oC |
Voltage
| UL Voltage Rating | 300 V |
|---|
Mechanical Characteristics
| Max. Pull Tension | 95 lbs (43 kg) |
|---|---|
| Bulk Cable Weight | 35 lbs/1000ft |
Temperature
| UL Temperature | 75°C |
|---|---|
| Operating | 0°C To +75°C |
Bend Radius
| Stationary Min. | 1.71 in (43.4 mm) |
|---|---|
| Installation Min. | 1.71 in |
Standards and Compliance
| Environmental Suitability | Indoor |
|---|---|
| Flammability / Reaction to Fire | NFPA 262 (UL910) |
| NEC / UL Compliance | Article 760, FPLP |
| European Directive Compliance | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
| Non-Plenum Number | 5100UL |
History
| Update and Revision | Revision Number: 0.308 Revision Date: 09-07-2025 |
|---|---|
| Footnote | C - CRATE REEL PUT-UP. |
Resources
Belden 6100UL technical datasheetSafe-T-Line Product BulletinFire Alarm Cable Product BulletinArmored Power-Limited Fire Alarm FPLPSound, Security & Alarm Cable Selection OverviewAccess Control Composite CablesNewGen Cables Product BulletinBelden Low Capacitance Digital Fire Alarm CablesWaterdog Cables Product BulletinDate: 2009-10-01
Related fire alarm cable

26120UL
Armored Fire Alarm, #14-2c BC, FPLP
2 · 14 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride

26220FL
Armored Fire Alarm, #16-2c BC, Shielded, FPLP
2 · 16 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride

26220UL
Armored Fire Alarm, #16-2c BC, FPLP
2 · 16 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride

26320FL
Armored Fire Alarm, #18-2c BC, Shielded, FPLP
2 · 18 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride