Fire Alarm, #18-4c BC, Shielded, FPLR
Fire Alarm Cable, Riser-FPLR, 4-18 AWG solid bare copper conductors with polyolefin insulation, overall Beldfoil® shield, PVC jacket with ripcord
- Availability
- Global
- Status
- Active
- Orderable items
- 2
Part numbers
5322FL is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.
| Item # | Color | UPC | Footnote | Order |
|---|---|---|---|---|
| 5322FL 0021000 | Red | 612825160618 | C | Order online |
| 5322FL 002U1000 | Red | 612825160601 | — | Order online |
Specifications
Product Overview
| Suitable Applications | Fire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification, Noisy Environment |
|---|
Construction Details
Conductor
| Element | Conductor(s) |
|---|---|
| No. of Elements | 4 |
| Size | 18 |
| Stranding | Solid |
| Material | BC - Bare Copper |
Insulation
| Material | PP - Polypropylene |
|---|---|
| Nom. Thickness | 0.007 in (0.18 mm) |
| Nom. Insulation Diameter | 0.056 in (1.4 mm) |
| Color Code | Black, Red, Brown, Blue |
Outer Shield
| Shield Type | Tape |
|---|---|
| Material | Bi-Laminate (Alum+Poly) |
| Coverage | 100% |
| Drainwire Type | 22 AWG (7x30) TC |
Outer Jacket
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nom. Thickness | 0.017 in (0.43 mm) |
| Nom. Diameter | 0.17 in |
| Ripcord | Yes |
Electrical Characteristics
| Nom Outer Shield DCR | 7.6 Ohm/1000ft (25 Ohm/km) |
|---|
Electricals
| Nom. Conductor DCR | 6.65 Ohm/1000ft |
|---|---|
| Nom. Capacitance Cond-to-Cond | 30 pF/ft (98 pF/m) |
| Nom. Capacitance Cond-to-Other (Conds + Shield) | 54 pF/ft (180 pF/m) |
| Max. Current | 3.5 Amps per Conductor at 25oC |
Voltage
| UL Voltage Rating | 300 V |
|---|
Mechanical Characteristics
| Max. Pull Tension | 78.4 lbs (35.6 kg) |
|---|---|
| Bulk Cable Weight | 29 lbs/1000ft |
Temperature
| UL Temperature | 75°C |
|---|---|
| Operating | -20°C To +75°C |
Bend Radius
| Stationary Min. | 2.55 in (64.8 mm) |
|---|---|
| Installation Min. | 2.55 in |
Standards and Compliance
| Environmental Suitability | Indoor |
|---|---|
| Flammability / Reaction to Fire | UL 1666 riser |
| NEC / UL Compliance | Article 760, FPLR |
| European Directive Compliance | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
| Other Standard Compliance(s) | California State Fire Marshall |
| Plenum Number | 6322FL |
History
| Update and Revision | Revision Number: 0.324 Revision Date: 09-07-2025 |
|---|---|
| Footnote | C - CRATE REEL PUT-UP. |
Resources
Belden 5322FL technical datasheetSafe-T-Line Product BulletinFire Alarm Cable Product BulletinArmored Power-Limited Fire Alarm FPLPSound, Security & Alarm Cable Selection OverviewAccess Control Composite CablesNewGen Cables Product BulletinBelden Low Capacitance Digital Fire Alarm CablesWaterdog Cables Product BulletinDate: 2005-04-01
Related fire alarm cable

26120UL
Armored Fire Alarm, #14-2c BC, FPLP
2 · 14 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride

26220FL
Armored Fire Alarm, #16-2c BC, Shielded, FPLP
2 · 16 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride

26220UL
Armored Fire Alarm, #16-2c BC, FPLP
2 · 16 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride

26320FL
Armored Fire Alarm, #18-2c BC, Shielded, FPLP
2 · 18 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride