Fire Alarm, #18-4c BC, FPLR

Fire Alarm Cable, Riser-FPLR, 4-18 AWG stranded bare copper conductors with polyolefin insulation, PVC jacket with ripcord

Availability
Americas
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

5302UL is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorUPCOrder
5302UL 002U1000Red612825159650Order online

Specifications

Product Overview

Suitable ApplicationsFire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification

Construction Details

Overall Cable Diameter (Nominal)0.184 in

Conductor

ElementConductor(s)
No. of Elements4
Size18 AWG
Stranding7x26
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialPP - Polypropylene
Nom. Thickness0.008 in (0.20 mm)
Nom. Insulation Diameter0.062 in (1.6 mm)
Color CodeBlack, Red, Brown, Blue

Outer Shield

MaterialNo Shield

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.017 in (0.43 mm)
Nom. Diameter0.184 in
RipcordYes

Electrical Characteristics

Electricals

ElementConductor(s)
Nom. Conductor DCR6.5 Ohm/1000ft
Nom. Capacitance Cond-to-Cond20.25 pF/ft (66.44 pF/m)
Max. Current4 Amps per Conductor at 25oC

Voltage

UL Voltage Rating300 V

Mechanical Characteristics

Max. Pull Tension89.5 lbs (40.6 kg)
Bulk Cable Weight28 lbs/1000ft

Temperature

UL Temperature75°C
Operating-20°C To +75°C

Bend Radius

Stationary Min.1.47 in (37.3 mm)
Installation Min.1.47 in

Standards and Compliance

Environmental SuitabilityIndoor
Flammability / Reaction to FireUL1666 Riser, FT4
NEC / UL ComplianceArticle 760, FPLR
European Directive ComplianceEU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)
Plenum Number6302UL

History