Belden Store
5300FL

Product Number: 5300FL

Fire Alarm, #18-2c BC, Shielded, FPLR

Fire Alarm Cable, Riser-FPLR, 2-18 AWG stranded bare copper conductors with polyolefin insulation, overall Beldfoil® shield, PVC jacket with ripcord

Availability
Americas
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

5300FL is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorUPCFootnoteOrder
5300FL 0021000Red612825159063COrder online
5300FL 002U1000Red612825159056—Order online

Specifications

Product Overview

Suitable ApplicationsFire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification, Noisy Environment

Construction Details

Overall Cable Diameter (Nominal)0.162 in

Conductor

ElementPair(s)
No. of Elements1
Size18 AWG
Stranding7x26
MaterialBC - Bare Copper

Insulation

ElementPair(s)
MaterialPP - Polypropylene
Nom. Thickness0.008 in (0.20 mm)
Nom. Insulation Diameter0.062 in (1.6 mm)
Color CodeBlack & Red

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type24 AWG (7x32) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.017 in (0.43 mm)
Nom. Diameter0.162 in
RipcordYes

Electrical Characteristics

Nom Outer Shield DCR16.25 Ohm/1000ft (53.31 Ohm/km)

Electricals

ElementPair(s)
Nom. Conductor DCR6.5 Ohm/1000ft
Nom. Capacitance Cond-to-Cond46.5 pF/ft (153 pF/m)
Nom. Capacitance Cond-to-Other (Conds + Shield)83.75 pF/ft (274.8 pF/m)
Max. Current5 Amps per Conductor at 25oC

Voltage

UL Voltage Rating300 V

Mechanical Characteristics

Max. Pull Tension50 lbs (23 kg)
Bulk Cable Weight18 lbs/1000ft

Temperature

UL Temperature75°C
Operating-20°C To +75°C

Bend Radius

Stationary Min.2.43 in (61.7 mm)
Installation Min.2.43 in

Standards and Compliance

Environmental SuitabilityIndoor
Flammability / Reaction to FireUL1666 Riser, FT4
NEC / UL ComplianceArticle 760, FPLR
European Directive ComplianceEU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)
Plenum Number6300FL

History

Update and RevisionRevision Number: 0.319 Revision Date: 09-07-2025
FootnoteC - CRATE REEL PUT-UP.

Resources

Related fire alarm cable