Belden Store
5220FN

Product Number: 5220FN

Fire Alarm, #16-2c BC, Shielded, NPLF

Fire Alarm Cable, Rated-NPLF, 2-16 AWG solid bare copper conductors with PVC/nylon insulation, overall Beldfoil® shield, PVC jacket with ripcord

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

5220FN is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorUPCFootnoteOrder
5220FN 0021000Red612825158349COrder online

Specifications

Product Overview

Suitable ApplicationsFire Alarm, Non-Power Limited, Circuits: Audio, Control, Initiating, Notification, Noisy Environment

Construction Details

Overall Cable Diameter (Nominal)0.266 in

Conductor

ElementConductor(s)
No. of Elements2
Size16 AWG
StrandingSolid
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.021 in (0.53 mm)
Nom. Insulation Diameter0.094 in (2.4 mm)
Color CodeBlack, Red

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type20 AWG (7x28) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.037 in (0.94 mm)
Nom. Diameter0.266 in
RipcordYes

Electrical Characteristics

Nom Outer Shield DCR7.1 Ohm/1000ft (23 Ohm/km)

Electricals

ElementConductor(s)
Nom. Conductor DCR4 Ohm/1000ft
Nom. Capacitance Cond-to-Cond48 pF/ft (160 pF/m)
Nom. Capacitance Cond-to-Other (Conds + Shield)86.4 pF/ft (283 pF/m)
Nom. Inductance0.19 μH/ft (0.62 μH/m)
Max. Current6.3 Amps per Conductor at 25oC

Voltage

UL Voltage Rating150 V

Mechanical Characteristics

Max. Pull Tension75 lbs (34 kg)
Bulk Cable Weight41 lbs/1000ft

Temperature

UL Temperature75°C
Operating-20°C To +75°C

Bend Radius

Stationary Min.3.99 in (101 mm)
Installation Min.3.99 in

Standards and Compliance

Environmental SuitabilityIndoor
Flammability / Reaction to FireUL1685 UL Loading
NEC / UL ComplianceArticle 760, NPLF
European Directive ComplianceEU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.318 Revision Date: 09-07-2025
FootnoteC - CRATE REEL PUT-UP.

Resources

Related fire alarm cable