Belden Store
5202UL

Product Number: 5202UL

Fire Alarm, #16-4c BC, FPLR

Fire Alarm Cable, Riser-FPLR, 4-16 AWG stranded bare copper conductors with polyolefin insulation, PVC jacket with ripcord

Availability
Americas
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

5202UL is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorUPCOrder
5202UL 002U1000Red612825158011Order online

Specifications

Product Overview

Suitable ApplicationsFire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification

Physical Characteristics (Overall)

Conductor Count4

Conductor

AWG16
Stranding19x29
MaterialBC - Bare Copper
No. of Conductors4

Insulation

MaterialPP - Polypropylene
Nominal Wall Thickness0.008 in

Color Chart

NumberColor
1Black
2Red
3Brown
4Blue

Outer Shield

MaterialNo Shield

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nominal Diameter0.21 in
Nominal Wall Thickness0.017 in
RipcordYes

Construction and Dimensions

Cabling

Twists3.4 twist/ft

Electrical Characteristics

Conductor DCR

Nominal Conductor DCR4.2 Ohm/1000ft

Capacitance

Nom. Capacitance Conductor to Conductor22.75 pF/ft

Current

Max. Recommended Current [A]8.8 Amps per Conductor at 25oC

Voltage

UL Voltage Rating300 V RMS

Temperature Range

UL Temperature Rating75°C
Operating Temperature Range-20°C To +75°C

Mechanical Characteristics

Bulk Cable Weight41 lbs/1000ft
Maximum Recommended Pulling Tension121.5 lbs
Minimum Minor Axis Bend Radius2.125 in

Standards

NEC ArticlesArticle 760
NEC/(UL) ComplianceFPLR

Applicable Environmental and Other Programs

EU Directive 2000/53/EC (ELV)Yes
EU Directive 2003/96/EC (BFR)Yes
EU Directive 2011/65/EU (RoHS 2)Yes
EU Directive 2012/19/EU (WEEE)Yes
EU Directive ComplianceEU Directive 2003/11/EC (BFR)
EU CE MarkYes
MII Order #39 (China RoHS)Yes

Flammability, LS0H, Toxicity Testing

UL FlammabilityUL1666 Riser
CSA FlammabilityFT4
UL voltage rating300 V RMS

Plenum/Non-Plenum

Plenum Number6202UL

History

Update and RevisionRevision Number: 0.169 Revision Date: 05-05-2023

Resources

Related fire alarm cable