Fire Alarm, #16-2c BC, FPLR
Fire Alarm Cable, Riser-FPLR, 2-16 AWG stranded bare copper conductors with polyolefin insulation, PVC jacket with ripcord
- Availability
- Global
- Status
- Active
- Orderable items
- 1
Part numbers
5200UL is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.
| Item # | Color | UPC | Order |
|---|---|---|---|
| 5200UL 002U1000 | Red | 612825157540 | Order online |
Specifications
Product Overview
| Suitable Applications | Fire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification |
|---|
Construction Details
| Overall Cable Diameter (Nominal) | 0.18 in |
|---|
Conductor
| Element | Pair(s) |
|---|---|
| No. of Elements | 1 |
| Size | 16 AWG |
| Stranding | 19x29 |
| Material | BC - Bare Copper |
Insulation
| Element | Pair(s) |
|---|---|
| Material | PP - Polypropylene |
| Nom. Thickness | 0.008 in (0.20 mm) |
| Nom. Insulation Diameter | 0.073 in (1.9 mm) |
| Color Code | Black & Red |
Outer Shield
| Material | No Shield |
|---|
Outer Jacket
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nom. Thickness | 0.017 in (0.43 mm) |
| Nom. Diameter | 0.18 in |
| Ripcord | Yes |
Electrical Characteristics
Electricals
| Nom. Conductor DCR | 4.2 Ohm/1000ft |
|---|---|
| Nom. Capacitance Cond-to-Cond | 22.75 pF/ft (74.64 pF/m) |
| Max. Current | 6.3 Amps per Conductor at 25oC |
Voltage
| UL Voltage Rating | 300 V |
|---|
Mechanical Characteristics
| Max. Pull Tension | 61 lbs (28 kg) |
|---|---|
| Bulk Cable Weight | 23 lbs/1000ft |
Temperature
| UL Temperature | 75°C |
|---|---|
| Operating | -20°C To +75°C |
Bend Radius
| Stationary Min. | 1.44 in (36.6 mm) |
|---|---|
| Installation Min. | 1.44 in |
Standards and Compliance
| Environmental Suitability | Indoor - Riser, Indoor |
|---|---|
| Flammability / Reaction to Fire | UL1666 Riser, FT4 |
| CPR Compliance | CPR Euroclass: Eca |
| NEC / UL Compliance | Article 760, FPLR |
| European Directive Compliance | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| UK Regulation Compliance | UKCA Mark |
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
| Plenum Number | 6200UL |
History
| Update and Revision | Revision Number: 0.315 Revision Date: 09-07-2025 |
|---|
Resources
Belden 5200UL technical datasheetSafe-T-Line Product BulletinFire Alarm Cable Product BulletinArmored Power-Limited Fire Alarm FPLPSound, Security & Alarm Cable Selection OverviewAccess Control Composite CablesNewGen Cables Product BulletinBelden Low Capacitance Digital Fire Alarm CablesWaterdog Cables Product BulletinDate: 2009-10-01
Related fire alarm cable

26120UL
Armored Fire Alarm, #14-2c BC, FPLP
2 · 14 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride

26220FL
Armored Fire Alarm, #16-2c BC, Shielded, FPLP
2 · 16 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride

26220UL
Armored Fire Alarm, #16-2c BC, FPLP
2 · 16 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride

26320FL
Armored Fire Alarm, #18-2c BC, Shielded, FPLP
2 · 18 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride