Belden Store
5122UL

Product Number: 5122UL

Fire Alarm, #14-4c BC, FPLR

Fire Alarm Cable, Riser-FPLR, 4-14 AWG solid bare copper conductors with polyolefin insulation, PVC jacket with ripcord

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

5122UL is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorUPCFootnoteOrder
5122UL 0021000Red612825157083COrder online

Specifications

Product Overview

Suitable ApplicationsFire Alarm, Monitor/Detection, Circuits: Audio, Control, Initiating, Notification

Construction Details

Overall Cable Diameter (Nominal)0.24 in

Conductor

ElementConductor(s)
No. of Elements4
Size14 AWG
StrandingSolid
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialPP - Polypropylene
Nom. Thickness0.010 in (0.25 mm)
Nom. Insulation Diameter0.085 in (2.2 mm)
Color CodeBlack, Red, Brown, Blue

Outer Shield

MaterialNo Shield

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.017 in (0.43 mm)
Nom. Diameter0.24 in
RipcordYes

Electrical Characteristics

Electricals

Nom. Conductor DCR2.62 Ohm/1000ft
Nom. Capacitance Cond-to-Cond23 pF/ft (75 pF/m)
Max. Current6.4 Amps per Conductor at 25oC

Voltage

UL Voltage Rating300 V

Mechanical Characteristics

Max. Pull Tension198.8 lbs (90.17 kg)
Bulk Cable Weight62 lbs/1000ft

Temperature

UL Temperature75°C
Operating-20°C To +75°C

Bend Radius

Stationary Min.1.92 in (48.8 mm)
Installation Min.1.92 in

Standards and Compliance

Environmental SuitabilityIndoor
Flammability / Reaction to FireUL1666 Riser
NEC / UL ComplianceArticle 760, FPLR
European Directive ComplianceEU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)
Other Standard Compliance(s)California State Fire Marshall
Plenum Number6122UL

History

Update and RevisionRevision Number: 0.308 Revision Date: 09-07-2025
FootnoteC - CRATE REEL PUT-UP.

Resources

Related fire alarm cable