Belden Store
5122FN

Product Number: 5122FN

Fire Alarm, #14-4c BC, Shielded, NPLF

Fire Alarm Cable, Rated-NPLF, 4-14 AWG solid bare copper conductors with PVC/nylon insulation, overall Beldfoil® shield, PVC jacket with ripcord

Availability
Global
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

5122FN is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorUPCOrder
5122FN 0021000Red612825157052Order online
5122FN 002500Red612825157069Order online

Specifications

Product Overview

Suitable ApplicationsFire Alarm, Non-Power Limited, Circuits: Audio, Control, Initiating, Notification, Noisy Environment

Construction Details

Conductor

Size14
StrandingSolid
MaterialBC - Bare Copper

Insulation

MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.021 in (0.53 mm)
Color CodeBlack, Red, Brown, Blue

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.042 in (1.1 mm)
Nom. Diameter0.348 in
RipcordYes

Electrical Characteristics

Nom Outer Shield DCR6.9 Ohm/1000ft (23 Ohm/km)

Electricals

Nom. Conductor DCR2.46 Ohm/1000ft (8.07 Ohm/km)
Nom. Capacitance Cond-to-Cond37.7 pF/ft (124 pF/m)
Nom. Capacitance Cond-to-Other (Conds + Shield)67.9 pF/ft (223 pF/m)
Max. Current6.4 Amps per Conductor at 25oC

Voltage

UL Voltage Rating150 V RMS

Mechanical Characteristics

Max. Pull Tension212.8 lbs (96.52 kg)
Bulk Cable Weight93.9 lbs/1000ft (140 kg/km)

Temperature

UL Temperature75°C
Operating-20°C To +75°C

Standards and Compliance

Environmental SuitabilityIndoor
Flammability / Reaction to FireUL1685 UL Loading
NEC / UL ComplianceArticle 760, NPLF
European Directive ComplianceEU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.314 Revision Date: 09-07-2025

Resources

Related fire alarm cable