Belden Store
5120FN

Product Number: 5120FN

Fire Alarm, #14-2c BC, Shielded, NPLF

Fire Alarm Cable, Rated-NPLF, 2-14 AWG solid bare copper conductors with PVC/nylon insulation, overall Beldfoil® shield, PVC jacket with ripcord

Availability
Global
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

5120FN is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorUPCOrder
5120FN 0021000Red612825156949Order online
5120FN 002500Red612825156956Order online

Specifications

Product Overview

Suitable ApplicationsFire Alarm, Non-Power Limited, Circuits: Audio, Control, Initiating, Notification, Noisy Environment

Construction Details

Overall Cable Diameter (Nominal)0.303 in

Conductor

ElementConductor(s)
No. of Elements2
Size14 AWG
StrandingSolid
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.021 in (0.53 mm)
Nom. Insulation Diameter0.108 in (2.74 mm)
Color CodeBlack, Red

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type20 AWG (7x28) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.042 in (1.1 mm)
Nom. Diameter0.303 in
RipcordYes

Electrical Characteristics

Nom Outer Shield DCR7.3 Ohm/1000ft (24 Ohm/km)

Electricals

Nom. Conductor DCR2.67 Ohm/1000ft
Nom. Capacitance Cond-to-Cond29.5 pF/ft (96.8 pF/m)
Nom. Capacitance Cond-to-Other (Conds + Shield)53.1 pF/ft (174 pF/m)
Nom. Inductance0.17 μH/ft (0.56 μH/m)
Max. Current8 Amps per Conductor at 25oC

Voltage

UL Voltage Rating150 V

Mechanical Characteristics

Max. Pull Tension113 lbs (51.3 kg)
Bulk Cable Weight56 lbs/1000ft

Temperature

UL Temperature75°C
Operating-20°C To +75°C

Bend Radius

Stationary Min.4.54 in (115 mm)
Installation Min.4.54 in

Standards and Compliance

Environmental SuitabilityIndoor
Flammability / Reaction to FireUL1685 UL Loading
NEC / UL ComplianceArticle 760, NPLF
European Directive ComplianceEU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.318 Revision Date: 09-07-2025

Resources

Related fire alarm cable