Fire Alarm, #14-2c BC, Shielded, FPL
Fire Alarm Cable, Rated-FPL, 2-14 AWG solid bare copper conductors with foam polyolefin insulation, overall Beldfoil® shield, PVC jacket with ripcord
- Availability
- Global
- Status
- Active
- Orderable items
- 1
Part numbers
5120FJ is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.
| Item # | Color | UPC | Footnote | Order |
|---|---|---|---|---|
| 5120FJ 0021000 | Red | 612825156901 | C | Order online |
Specifications
Product Overview
| Suitable Applications | Fire Alarm, Addressable Systems, Circuits: Audio, Control, Initiating, Notification, Noisy Environment |
|---|
Construction Details
| Overall Cable Diameter (Nominal) | 0.279 in |
|---|
Conductor
| Element | Pair(s) |
|---|---|
| No. of Elements | 1 |
| Size | 14 AWG |
| Stranding | Solid |
| Material | BC - Bare Copper |
Insulation
| Element | Pair(s) |
|---|---|
| Material | PE - Polyethylene (Foam) |
| Nom. Thickness | 0.02 in (0.51 mm) |
| Nom. Insulation Diameter | 0.104 in (2.64 mm) |
| Color Code | Black & Red |
Outer Shield
| Shield Type | Tape |
|---|---|
| Material | Bi-Laminate (Alum+Poly) |
| Coverage | 100% |
| Drainwire Type | 20 AWG (7x28) TC |
Outer Jacket
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nom. Thickness | 0.033 in (0.84 mm) |
| Nom. Diameter | 0.279 in |
| Ripcord | Yes |
Electrical Characteristics
| Nom Outer Shield DCR | 8.1 Ohm/1000ft (27 Ohm/km) |
|---|
Electricals
| Nom. Conductor DCR | 2.67 Ohm/1000ft |
|---|---|
| Nom. Capacitance Cond-to-Cond | 29.5 pF/ft (96.8 pF/m) |
| Nom. Capacitance Cond-to-Other (Conds + Shield) | 53.1 pF/ft (174 pF/m) |
| Nom. Inductance | 0.17 μH/ft (0.56 μH/m) |
| Max. Current | 8 Amps per Conductor at 25oC |
Voltage
| UL Voltage Rating | 300 V |
|---|
Mechanical Characteristics
| Max. Pull Tension | 112 lbs (50.8 kg) |
|---|---|
| Bulk Cable Weight | 46 lbs/1000ft |
Temperature
| UL Temperature | 75°C |
|---|---|
| Operating | -20°C To +75°C |
Bend Radius
| Stationary Min. | 4.18 in (106 mm) |
|---|---|
| Installation Min. | 4.18 in |
Standards and Compliance
| Environmental Suitability | Indoor |
|---|---|
| Flammability / Reaction to Fire | UL1685 UL Loading |
| NEC / UL Compliance | Article 760, FPL |
| European Directive Compliance | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
History
| Update and Revision | Revision Number: 0.323 Revision Date: 09-07-2025 |
|---|---|
| Footnote | C - CRATE REEL PUT-UP. |
Resources
Belden 5120FJ technical datasheetSafe-T-Line Product BulletinFire Alarm Cable Product BulletinArmored Power-Limited Fire Alarm FPLPSound, Security & Alarm Cable Selection OverviewAccess Control Composite CablesNewGen Cables Product BulletinBelden Low Capacitance Digital Fire Alarm CablesWaterdog Cables Product BulletinDate: 2004-01-01
Related fire alarm cable

26120UL
Armored Fire Alarm, #14-2c BC, FPLP
2 · 14 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride

26220FL
Armored Fire Alarm, #16-2c BC, Shielded, FPLP
2 · 16 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride

26220UL
Armored Fire Alarm, #16-2c BC, FPLP
2 · 16 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride

26320FL
Armored Fire Alarm, #18-2c BC, Shielded, FPLP
2 · 18 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride