Fire Alarm, #12-2c BC, Shielded, NPLF
Fire Alarm Cable, Rated-NPLF, 2-12 AWG solid bare copper conductors with PVC/nylon insulation, overall Beldfoil® shield, PVC jacket with ripcord
- Availability
- Global
- Status
- Active
- Orderable items
- 1
Part numbers
5020FN is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.
| Item # | Color | UPC | Order |
|---|---|---|---|
| 5020FN 002500 | Red | 612825155904 | Order online |
Specifications
Product Overview
| Suitable Applications | Fire Alarm, Non-Power Limited, Circuits: Audio, Control, Initiating, Notification, Noisy Environment |
|---|
Construction Details
Conductor
| Size | 12 |
|---|---|
| Stranding | Solid |
| Material | BC - Bare Copper |
Insulation
| Material | PVC/Nylon - Polyvinyl Chloride + Nylon |
|---|---|
| Nom. Thickness | 0.021 in (0.53 mm) |
| Color Code | Black, Red |
Outer Shield
| Shield Type | Tape |
|---|---|
| Material | Bi-Laminate (Alum+Poly) |
| Coverage | 100% |
Outer Jacket
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nom. Thickness | 0.042 in (1.1 mm) |
| Nom. Diameter | 0.337 in |
| Ripcord | Yes |
Electrical Characteristics
| Nom Outer Shield DCR | 6.9 Ohm/1000ft (23 Ohm/km) |
|---|
Electricals
| Nom. Conductor DCR | 1.58 Ohm/1000ft (5.18 Ohm/km) |
|---|---|
| Nom. Capacitance Cond-to-Cond | 66.9 pF/ft (219 pF/m) |
| Nom. Capacitance Cond-to-Other (Conds + Shield) | 120.4 pF/ft (395.0 pF/m) |
| Nom. Inductance | 0.16 μH/ft (0.52 μH/m) |
| Max. Current | 12 Amps per Conductor at 25oC |
Voltage
| UL Voltage Rating | 150 V RMS |
|---|
Mechanical Characteristics
| Max. Pull Tension | 172 lbs (78.0 kg) |
|---|---|
| Bulk Cable Weight | 73.4 lbs/1000ft (109 kg/km) |
Temperature
| UL Temperature | 75°C |
|---|---|
| Operating | -20°C To +75°C |
Standards and Compliance
| Environmental Suitability | Indoor |
|---|---|
| Flammability / Reaction to Fire | UL1685 UL Loading |
| NEC / UL Compliance | Article 760, NPLF |
| European Directive Compliance | EU CE Mark, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
History
| Update and Revision | Revision Number: 0.314 Revision Date: 09-07-2025 |
|---|
Resources
Belden 5020FN technical datasheetSafe-T-Line Product BulletinFire Alarm Cable Product BulletinArmored Power-Limited Fire Alarm FPLPSound, Security & Alarm Cable Selection OverviewAccess Control Composite CablesNewGen Cables Product BulletinBelden Low Capacitance Digital Fire Alarm CablesWaterdog Cables Product BulletinDate: 2005-07-01
Related fire alarm cable

26120UL
Armored Fire Alarm, #14-2c BC, FPLP
2 · 14 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride

26220FL
Armored Fire Alarm, #16-2c BC, Shielded, FPLP
2 · 16 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride

26220UL
Armored Fire Alarm, #16-2c BC, FPLP
2 · 16 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride

26320FL
Armored Fire Alarm, #18-2c BC, Shielded, FPLP
2 · 18 AWG · BC - Bare Copper · PVC - Polyvinyl Chloride