Belden Store
9487

Product Number: 9487

High Perform Instr, 1 Pr #16 Str TC, PVC-NYL Ins E2, Blk PVC Jkt, 600V TC

High Performance Instrumentation, 1 Pair 16AWG (19x29) Tinned Copper, PVC-NYL Insulation E2 Color Code, Black PVC Outer Jacket, 600V TC

Availability
Global
Status
Active
Orderable items
3

Ships from and sold by A5 IT.

Part numbers

9487 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorUPCFootnoteOrder
9487 0101000Black612825253785COrder online
9487 010500Black612825253792COrder online
9487 0105000Black612825253808C ZOrder online

Specifications

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners

Construction Details

Overall Cable Diameter (Nominal)0.295 in (7.49 mm)

Conductor

ElementPair(s)
No. of Elements1
Size16 AWG
Stranding19x29
MaterialTC - Tinned Copper

Insulation

ElementPair(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.022 in (0.56 mm)
Nom. Insulation Diameter0.101 in (2.57 mm)
Color CodeBlack, Red

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.048 in (1.2 mm)
Nom. Diameter0.295 in (7.49 mm)
RipcordYes

Electrical Characteristics

Electricals

ElementPair(s)
Nom. Conductor DCR4.45 Ohm/1000ft
Nom. Capacitance Cond-to-Cond26 pF/ft (85 pF/m)
Nom. Inductance0.15 μH/ft (0.49 μH/m)
Max. Current6.2 Amps per conductor at 25°C

Voltage

UL Voltage Rating600 V (TC), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension70 lbs (32 kg)
Bulk Cable Weight51 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
Operating-30°C to +90°C Dry, 75°C wet

Bend Radius

Stationary Min.1.2 in (30 mm)
Installation Min.1.2 in (30 mm)

Standards and Compliance

Environmental SuitabilityIndoor/Outdoor, Indoor, Outdoor, Sunlight Resistance
Flammability / Reaction to FireUL 1685 UL Loading, IEEE 1202, FT4
CPR ComplianceCPR Euroclass: Eca
NEC / UL ComplianceArticle 336, Article 760, NPLF, TC
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
UK Regulation ComplianceUKCA Mark
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.596 Revision Date: 09-07-2025
FootnoteC - CRATE REEL PUT-UP., Z - FINAL PUT-UP MAY VARY (= OR -) 10% FOR SPOOLS OR REELS AND (+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.

Resources

Related pvc cable