Belden Store
9344

Product Number: 9344

High Perform Instr, 1 Pr #12 Str TC, PVC-NYL Ins E2, OS, Blk PVC Jkt, 600V TC

High Performance Instrumentation, 1 Pair 12AWG (37x27) Tinned Copper, PVC-NYL Insulation E2 Color Code, Overall Beldfoil® Shield, Black PVC Outer Jacket, 600V TC

Availability
Global
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

9344 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorUPCFootnoteOrder
9344 0101000Black612825232223COrder online
9344 010500Black612825232230COrder online

Specifications

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners

Construction Details

Overall Cable Diameter (Nominal)0.384 in (9.75 mm)

Conductor

ElementPair(s)
No. of Elements1
Size12 AWG
Stranding37x27
MaterialTC - Tinned Copper

Insulation

ElementPair(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.027 in (0.69 mm)
Nom. Insulation Diameter0.145 in (3.68 mm)
Color CodeICEA Chart E2

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type12 AWG (19x25) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.045 in (1.1 mm)
Nom. Diameter0.384 in (9.75 mm)
RipcordYes

Electrical Characteristics

Nom Outer Shield DCR1.72 Ohm/1000ft (5.64 Ohm/km)

Electricals

ElementPair(s)
Nom. Conductor DCR1.65 Ohm/1000ft
Nom. Capacitance Cond-to-Cond56 pF/ft (180 pF/m)
Nom. Capacitance Cond-to-Other (Conds + Shield)106 pF/ft (348 pF/m)
Nom. Inductance0.19 μH/ft (0.62 μH/m)
Max. Current8.24 Amps per Conductor at 25oC

Voltage

UL Voltage Rating600 V (TC), 150 V (NPLF)

Mechanical Characteristics

Max. Pull Tension245 lbs (111 kg)
Bulk Cable Weight106 lbs/1000ft

Temperature

UL Temperature90°C Dry, 90°C Wet
Operating-30°C to +90°C Dry, 75°C wet

Bend Radius

Stationary Min.3.8 in (97 mm)
Installation Min.3.8 in (97 mm)

Standards and Compliance

Environmental SuitabilityIndoor/Outdoor, Indoor, Outdoor, Sunlight Resistance, Burial
Flammability / Reaction to FireUL 1685 UL Loading, IEEE 1202, FT4
NEC / UL ComplianceArticle 336, Article 760, NPLF, TC
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.600 Revision Date: 09-07-2025
FootnoteC - CRATE REEL PUT-UP.

Resources

Related pvc cable