Belden Store
3092T

Product Number: 3092T

ControlBusTM, Coax RG6, #18 Sol BCCS, PO Ins, QUAD AL Shld, LSZH Jkt, CMG

ControlBusTM, Coax RG6 18AWG (Solid) Bare Copper Covered Steel, PO Insulation, Overall Duofoil®+ Aluminum Braid(60%)+Overall Duofoil®+Aluminum Braid(40%) Shield, LSZH Outer Jacket, CMG

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

3092T is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorUPCOrder
3092T 0105000Black612825141433Order online

Specifications

Product Overview

Suitable Applicationsharsh environment, factory automation, ControlNetTM, Modbus II, Industrial Coax, Belden ControlNet cables provide maximum signal integrity and run length exceeding the high-speed, time-critical requirements necessary for ControlNet factory floor applications

Construction Details

RG Type6
Outer Jacket1 Table NotesFlame Retardant

Conductor

Size18
StrandingSolid
Nom. Diameter0.040 in
MaterialBCCS - Bare Copper Covered Steel

Insulation

MaterialPE - Polyethylene (Foam)
Nom. Insulation Diameter0.180 in (4.57 mm)

Outer Shield

LayerOuter Shield TypeMaterialMaterial Trade NameCoverage
1TapeTri-Laminate (Alum+Poly+Alum)Duobond® II100%
2BraidAluminum60%
3TapeTri-Laminate (Alum+Poly+Alum)Duofoil®100%
4BraidAluminum60%

Outer Jacket

MaterialPE - Polyethylene
Nom. Diameter0.3 in

Electrical Characteristics

Return Loss

Frequency5-50 MHz
Min. Structural Return Loss23 dB

Attenuation

FrequencyNom. Attenuation
1 MHz0.35 dB/100ft
2 MHz0.38 dB/100ft
5 MHz0.45 dB/100ft
10 MHz0.59 dB/100ft
20 MHz0.86 dB/100ft
50 MHz1.37 dB/100ft
100 MHz1.97 dB/100ft
200 MHz2.82 dB/100ft
300 MHz3.48 dB/100ft
400 MHz4.04 dB/100ft

Electricals

Nom. Conductor DCR28 Ohm/1000ft (92 Ohm/km)
Nom. Capacitance Cond-to-Shield16.2 pF/ft (53.1 pF/m)
Nom. Characteristic Impedance75 Ohm
Nom. Velocity of Prop.83%

Voltage

UL Voltage Rating300 V RMS

Mechanical Characteristics

Max. Pull Tension162 lbs (73.5 kg)
Bulk Cable Weight35 lbs/1000ft (52 kg/km)

Temperature

UL Temperature75°C
Operating-20°C To +75°C

Standards and Compliance

Flammability / Reaction to Fire1202, IEC 60332-3-22
NEC / UL ComplianceCL2, CMG
CEC / C(UL) ComplianceCMG.
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.333 Revision Date: 02-20-2026

Resources

Related controlnet cable