Belden Store
Belden9843LS

Product Number: 9843LS

RS-485, 3PR #24 Str TC, PO ins, F/B, LSZH Jkt, 300V, SWA

RS-485, 3 Pair AWG 24 Tinned Copper - Stranded, Polyolefin (PO, PE, PP) insulation, Foil + Braid(s) shielding, LSZH / FRNC jacket , 300V, SWA

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

9843LS is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorPutup TypeLengthEANOrder
9843LS.00500BlackReel500 m8719605127235Order online

Specifications

Product Overview

Suitable ApplicationsRS-485, POS; Computer communications; Low Voltage Analog Signals (4-20ma, 0-10v, ...); Low Voltage Digital Control (24v, ...); Line Level Audio; Panel Wiring; serial communication (RS-485 standard) comprising of PLCs, VFDs, HMIs, motors, RTU, SCADA, etc. within noisy environments over long distance, etc.

Construction Details

Overall Cable Diameter (Nominal)13.5 mm (0.531 in)

Conductor

ElementPair(s)
No. of Elements3
Size24 AWG
Stranding7x32
MaterialTC - Tinned Copper

Insulation

ElementPair(s)
MaterialPE - Polyethylene
Nom. Thickness0.56 mm (0.022 in)
Nom. Insulation Diameter1.73 mm (0.0681 in)
Color CodeWhite/Blue & Blue/White, White/Orange & Orange/White, White/Green & Green/White

Outer Shield

Shield TypeMaterialCoverageDrainwire Type
TapeBi-Laminate (Alum+Poly)100%24 AWG (7x32) TC
BraidTinned Copper (TC)90%

Inner Jacket

MaterialLSZH - Low Smoke Zero Halogen (Flame Retardant)
Nom. Thickness0.9 mm (0.035 in)
Nom. Diameter9.1 mm (0.36 in)

Armor

Armor Type & MaterialSWA - Steel Wire Armor
Armor Thickness0.9 mm
CoverageMin. 95%

Outer Jacket

MaterialLSZH - Low Smoke Zero Halogen (Flame Retardant)
Nom. Thickness1.3 mm (0.051 in)
Nom. Diameter13.5 mm (0.531 in)

Electrical Characteristics

Nom Outer Shield DCR7.2 Ohm/km (2.2 Ohm/1000ft)

Electricals

ElementPair(s)
Nom. Conductor DCR78.7 Ohm/km (24.0 Ohm/1000ft)
Nom. Capacitance Cond-to-Cond42 pF/m (13 pF/ft)
Nom. Capacitance Cond-to-Other (Conds + Shield)75.5 pF/m (23.0 pF/ft)
Nom. Characteristic Impedence120 Ohm
Nom. Delay5.2 ns/m
Nom. Velocity of Prop.66%
Max. Current2.1 Amps per Conductor

High Frequency (Nominal/Typical)

ElementPair(s)
Frequency [MHz]1
Nom. Insertion Loss (Attenuation) [dB/100m]1.97

Voltage

Voltage Rating300 V

Mechanical Characteristics

Max. Pull Tension500 N (110 lbf)
Bulk Cable Weight324 kg/km (218 lbs/1000ft)

Temperature

Operating-45°C To +80°C
Installation-15°C To +80°C
Storage-45°C To +80°C

Bend Radius

Stationary Min.133 mm (5.24 in)
Installation Min.202.5 mm (7.972 in)

Standards and Compliance

Environmental SuitabilityIndoor Indoor/Outdoor Outdoor Indoor/Outdoor - Euroclass Eca, Indoor, Outdoor, Non-Halogenated, Sunlight Resistance, Oil Resistance - IRM 902 70°Cx4h, Oil Resistance - IEC 60811-404
Flammability / Reaction to FireIEC 60332-3-24, IEC 60332-1-2
CPR ComplianceCPR Euroclass: Eca
CENELEC ComplianceEN 50290-2-20
European Halogen Free StandardsIEC 62821-1 Halogen Free Compliance = Yes, IEC 60754-1 - Halogen Amount = Zero, IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity = 2.5 μS/mm, IEC 60754-2 - Halogen Acid Gas Amount - Min. pH = 4.3, IEC 61034-2 - Smoke Density Min. Transmittance = 60%
European Directive ComplianceEU CE Mark
UK Regulation ComplianceUKCA Mark
Other Standard Compliance(s)DMX-512

History

Update and RevisionRevision Number: 0.230 Revision Date: 07-23-2026

Resources

Related industrial ethernet cable