Teck90 1000V, 4+G C #2+6 Str BC, XLPE Ins M4, PVC Jkt, AIA Armor, Blk PVC Jkt, CSA HL SUN RES -40C
Teck90 1000V, 4+G Conductor 2+6AWG (7x10H) Bare Copper, XLPE Insulation M4 Color Code, PVC Inner Jacket, Aluminum Interlock Armor, Black PVC Outer Jacket, CSA HL SUN RES -40C
- Availability
- Global
- Status
- Active
- Orderable items
- 2
Part numbers
C5622 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.
| Item # | Putup Type | UPC | Order |
|---|---|---|---|
| C5622 0102460 | Reel | 612825283935 | Order online |
| C5622 0102500 | Reel | — | Order online |
Specifications
Product Overview
| Suitable Applications | Power and Control Applications up to 600V |
|---|
Construction Details
| Overall Cable Diameter (Nominal) | 1.521 in |
|---|
Conductor
| Element | No. of Elements | Size | Stranding | Material |
|---|---|---|---|---|
| Conductor(s) | 4 | 2 AWG | 7x10 | BC - Bare Copper |
| Ground Wire | 1 | 6 AWG | 7x14 | BC - Bare Copper |
Insulation
| Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|---|---|---|---|
| Conductor(s) | XLP, XLPO, XLPE (Thermoset) | 0.06 in (1.5 mm) | 0.405 in mm | Red, Black, Blue, White |
| Ground Wire | No Insulation |
Outer Shield
| Material | No Shield |
|---|
Inner Jacket
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nom. Thickness | 0.083 in (2.1 mm) |
| Nom. Diameter | 1.155 in (29.34 mm) |
Armor
| Armor Type & Material | AIA - Aluminum Interlock Armor |
|---|---|
| Diameter Over Armor | 1.415 in (35.94 mm) |
Outer Jacket
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nom. Thickness | 0.053 in (1.3 mm) |
| Nom. Diameter | 1.521 in |
| Ripcord | Yes |
Electrical Characteristics
Electricals
| Element | Nom. Conductor DCR | Max. Current |
|---|---|---|
| Conductor(s) | 0.166 Ohm/1000ft | 104 Amps per Conductor at 30oC |
| Ground Wire | 0.419 Ohm/1000ft (1.37 Ohm/km) |
Voltage
| Voltage Rating | 1000 V (TECK 90) |
|---|
Mechanical Characteristics
| Max. Pull Tension | 3746.3 lbs (1699.3 kg) |
|---|---|
| Bulk Cable Weight | 1556 lbs/1000ft |
Temperature
| Operating | -40°C To +90°C |
|---|---|
| Installation | -25°C To +90°C |
Bend Radius
| Stationary Min. | 12.09 in (307.1 mm) |
|---|---|
| Installation Min. | 12.09 in |
Standards and Compliance
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Burial |
|---|---|
| CEC / C(UL) Compliance | TECK 90, HL. |
| European Directive Compliance | EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
History
| Update and Revision | Revision Number: 0.237 Revision Date: 05-31-2024 |
|---|
Resources
Related control cable

1285
RW90 1000V, 4 Str BC, XLPE Ins, 90C Dry/Wet CSA HL SUN RES
1 · BC - Bare Copper · XLP, XLPO, XLPE (Thermoset) · PVC - Polyvinyl Chloride

19105
Portable Cordage, 3 C #10 Str BC, EPDM Ins, Rubber Jkt, UL Type S
3 · 10 AWG · BC - Bare Copper · EPDM - Ethylene Propylene Diene Monomer

19106
Portable Cordage, 3 C #12 Str BC, EPDM Ins, Rubber Jkt, UL Type S
3 · 12 AWG · BC - Bare Copper · EPDM - Ethylene Propylene Diene Monomer

19107
Portable Cordage, 3 C #14 Str BC, EPDM Ins, Rubber Jkt, UL Type S
3 · 14 AWG · BC - Bare Copper · EPDM - Ethylene Propylene Diene Monomer