VFD 300% Gnd, 3C+G #12 Str TC, XLPE Ins+PVC Gnd, OS+TC Brd w/#12 TC Drain, Blk PVC Jkt, 2000V TC-ER 90C Dry/Wet 2000V Flexible Motor Supply Cable WTTC
Belden 300% Ground Flexible VFD, 3 Conductor 12AWG (65x30) Tinned Copper, XLPE Insulation M4 Color Code+PVC Insulated Ground, Overall Beldfoil®+Tinned Copper Braid(85%) Shield w/12AWG Tinned Copper Drain, Black PVC Outer Jacket, 2000V TC-ER 90C Dry/Wet 2000V Flexible Motor Supply Cable WTTC 1000V CSA AWM I/II A/B 600V CIC TC SUN RES DIR BUR Oil Resistant
- Availability
- Global
- Status
- Active
- Orderable items
- 2
Part numbers
29537 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.
| Item # | Color | Putup Type | Length | UPC | Order |
|---|---|---|---|---|---|
| 29537 0101000 | Black | Reel | 1,000 ft | 612825138419 | Order online |
| 29537 0105000 | Black | Reel | 5,000 ft | 612825138426 | Order online |
Specifications
Information
| Put-Up Type | Reel |
|---|---|
| Update and Revision | Revision Number: 0.541 Revision Date: 02-20-2026 |
Product Overview
| Suitable Applications | Variable Frequency Drives (VFD); AC Motor and Drive Systems; High voltage requirements |
|---|
Construction Details
| Overall Cable Diameter (Nominal) | 0.723 in (18.4 mm) |
|---|
Conductor
| Element | No. of Elements | Size | Stranding | Material |
|---|---|---|---|---|
| Conductor(s) | 3 | 12 AWG | 65x30 | TC - Tinned Copper |
| Ground Wire | 1 | 12 AWG | 65x30 | TC - Tinned Copper |
Insulation
| Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|---|---|---|---|
| Conductor(s) | XLPE - Cross-Linked Polyethylene (Thermoset) | 0.066 in (1.7 mm) | 0.225 in (5.72 mm) | ICEA Chart M4 |
| Ground Wire | XLPE - Cross-Linked Polyethylene (Thermoset) | 0.066 in (1.7 mm) | 0.225 in (5.72 mm) | Green/Yellow Stripe |
Outer Shield
| Shield Type | Material | Coverage | Drainwire Type |
|---|---|---|---|
| Tape | Tri-Laminate (Alum+Poly+Alum) | 100% | 12 AWG (65x30) TC |
| Braid | Tinned Copper (TC) | 85% |
Outer Jacket
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nom. Thickness | 0.073 in (1.9 mm) |
| Nom. Diameter | 0.723 in (18.4 mm) |
| Ripcord | Yes |
Electrical Characteristics
| Nom Outer Shield DCR | 0.68 Ohm/1000ft (2.2 Ohm/km) |
|---|
Electricals
| Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Nom. Characteristic Impedence | Nom. Inductance | Nom. Velocity of Prop. | Max. Current |
|---|---|---|---|---|---|---|---|
| Conductor(s) | 1.569 Ohm/1000ft | 54 pF/ft (180 pF/m) | 97 pF/ft (320 pF/m) | 44 Ohm | 0.197 μH/ft (0.646 μH/m) | 55% | 30 Amps per Conductor at 30oC |
| 1.72 Ohm/1000ft (5.64 Ohm/km) | 30 Amps per Conductor at 30oC |
Voltage
| UL Voltage Rating | 2000 V (TC, C(UL) TC), 1000 V (WTTC, UL Flexible Motor Supply Cable, CSA AWM I/II A/B) |
|---|
Mechanical Characteristics
| Max. Pull Tension | 7922 lbs (3593 kg) |
|---|---|
| Bulk Cable Weight | 336 lbs/1000ft |
Temperature
| UL Temperature | 90°C Dry, 90°C Wet |
|---|---|
| Operating | -40°C To +90°C |
Bend Radius
| Stationary Min. | 8.7 in (220 mm) |
|---|---|
| Installation Min. | 8.7 in (220 mm) |
Standards and Compliance
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Burial |
|---|---|
| Sustainability | CA Prop 65 |
| Flammability / Reaction to Fire | UL 1685 UL Loading, FT4, IEEE 1202 FT4 |
| NEC / UL Compliance | Article 336, TC-ER, WTTC, UL Flexible Motor Supply Cable |
| AWM Compliance | AWM I/II A/B |
| ICEA Compliance | S-95-658 |
| European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
| Other Standard Compliance(s) | P-07-KA070003-MSHA |
History
| Update and Revision | Revision Number: 0.541 Revision Date: 02-20-2026 |
|---|
Resources
Related vfd cable

29500
VFD 300% Gnd, 3C+G #16 Str TC, XLPE Ins+PVC Gnd, OS+TC Brd w/#16 TC Ground/Drain, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable WTTC
PVC - Polyvinyl Chloride · 600 V RMS (Type TC) (TC-ER, WTTC, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC) · 90°C Dry, 90°C Wet

29500T
VFD 300% Gnd, 3C+G #16 Str TC, XLPE Ins+PVC Grd, OS+TC Brd w/#16 TC Drain, Blk LSZH Jkt, 600V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable WTTC
LSZH - Low Smoke Zero Halogen (Flame Retardant) · 1000 V (TC, WTTC, UL Flexible Motor Supply Cable) · 90°C Dry, 90°C Wet

29501
VFD 300% Gnd, 3C+G #14 Str TC, XLPE Ins+PVC Gnd, OS+TC Brd w/#14 TC Ground/Drain, Blk PVC Jkt, 600/1000V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable WTTC
PVC - Polyvinyl Chloride · 1000 V (TC-ER, WTTC,UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC) · 90°C Dry, 90°C Wet

29501T
VFD 300% Gnd, 3C+G #14 Str TC, XLPE Ins+PVC Grd, OS+TC Brd w/#14 TC Drain, Blk LSZH Jkt, 600/1000V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable WTTC
LSZH - Low Smoke Zero Halogen (Flame Retardant) · 1000 V (TC, WTTC, UL Flexible Motor Supply Cable) · 90°C Dry, 90°C Wet