600V ACIC, (12) 16 AWG (7x24) BC+Grd, XLPE/PVC/PVC, AIA Armor
Twelve 16 AWG stranded (7x24) bare copper conductors plus bare copper ground wire, cross-linked polyethylene insulation, PVC inner jacket, aluminum interlocked armor, PVC outer jacket.
- Availability
- Global
- Status
- Active
- Orderable items
- 2
Part numbers
29006 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.
| Item # | Order |
|---|---|
| 29006 J221968 | Order online |
| 29006 J222952 | Order online |
Specifications
Product Overview
| Suitable Applications | Power and Control Applications up to 600V |
|---|
Construction Details
| Inner Jacket Table Notes | Separator-CORR. MYLAR Tape |
|---|---|
| Overall Cable Diameter (Nominal) | 0.980 in |
Conductor
| Element | No. of Elements | Size | Stranding | Material |
|---|---|---|---|---|
| Conductor(s) | 12 | 16 AWG | 7x24 | BC - Bare Copper |
| Ground Wire | 1 | 16 AWG | 7x24 | BC - Bare Copper |
Insulation
| Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|---|---|---|---|
| Conductor(s) | XLP, XLPO, XLPE (Thermoset) | 0.030 in (0.76 mm) | 0.118 in (3.00 mm) | White and Numbered, Black and Numbered |
| Ground Wire | XLP, XLPO, XLPE (Thermoset) | 0.030 in (0.76 mm) | 0.118 in (3.00 mm) | Green |
Outer Shield
| Material | No Shield |
|---|
Inner Jacket
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nom. Thickness | 0.63 in (16 mm) |
| Nom. Diameter | 0.651 in (16.5 mm) |
| Ripcord | Yes |
| Color | Black |
Armor
| Armor Type & Material | AIA - Aluminum Interlock Armor |
|---|---|
| Armor Thickness | 0.025 in (0.64 mm) |
| Diameter Over Armor | 0.876 in (22.3 mm) |
Outer Jacket
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nom. Thickness | 0.052 in (1.3 mm) |
| Nom. Diameter | 0.980 in |
Electrical Characteristics
Electricals
| Element | Nom. Conductor DCR | Max. Current |
|---|---|---|
| Conductor(s) | 4.45 Ohm/1000ft | 12.6 Amps per Conductor at 30oC |
| Ground Wire | 4.45 Ohm/1000ft (14.6 Ohm/km) | 19 Amps per Conductor at 25oC |
Voltage
| Voltage Rating | 600 V |
|---|
Mechanical Characteristics
| Max. Pull Tension | 464.1 lbs (210.5 kg) |
|---|---|
| Bulk Cable Weight | 425 lbs/1000ft |
Temperature
| Operating | -40°C To +90°C |
|---|
Bend Radius
| Stationary Min. | 11.76 in (298.7 mm) |
|---|---|
| Installation Min. | 11.76 in |
Standards and Compliance
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Burial |
|---|---|
| CEC / C(UL) Compliance | HL, ACIC. |
| European Directive Compliance | EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
History
| Update and Revision | Revision Number: 0.201 Revision Date: 05-31-2024 |
|---|
Resources
Related acic cable

22603D
CIC 300V, 1 Tri #16 Str BC, XLPE Ins E1, OS, Blk PVC Jkt, 90C Dry/Wet SUN RES -25C

22635
CIC 300V, 8 Pr #18 Str TC, PVC Ins E1, IS/OS, Blk PVC Jkt, 105C Dry 75C Wet SUN RES -25C
TC - Tinned Copper · PVC - Polyvinyl Chloride

22645
CIC 300V, 1 Pr #18 Str TC, PVC Ins E1, OS, Blk PVC Jkt, 105C Dry 75C Wet SUN RES -25C
TC - Tinned Copper · PVC - Polyvinyl Chloride · 300 V RMS

22677
CIC 300V, 1 Tri #18 Str TC, PVC Ins E1, OS, Blk PVC Jkt, 105C Dry 75C Wet SUN RES -25C
TC - Tinned Copper · PVC - Polyvinyl Chloride