Product Number: 29006

600V ACIC, (12) 16 AWG (7x24) BC+Grd, XLPE/PVC/PVC, AIA Armor

Twelve 16 AWG stranded (7x24) bare copper conductors plus bare copper ground wire, cross-linked polyethylene insulation, PVC inner jacket, aluminum interlocked armor, PVC outer jacket.

Availability
Global
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

29006 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Order
29006 J221968Order online
29006 J222952Order online

Specifications

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V

Construction Details

Inner Jacket Table NotesSeparator-CORR. MYLAR Tape
Overall Cable Diameter (Nominal)0.980 in

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Conductor(s)1216 AWG7x24BC - Bare Copper
Ground Wire116 AWG7x24BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)XLP, XLPO, XLPE (Thermoset)0.030 in (0.76 mm)0.118 in (3.00 mm)White and Numbered, Black and Numbered
Ground WireXLP, XLPO, XLPE (Thermoset)0.030 in (0.76 mm)0.118 in (3.00 mm)Green

Outer Shield

MaterialNo Shield

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.63 in (16 mm)
Nom. Diameter0.651 in (16.5 mm)
RipcordYes
ColorBlack

Armor

Armor Type & MaterialAIA - Aluminum Interlock Armor
Armor Thickness0.025 in (0.64 mm)
Diameter Over Armor0.876 in (22.3 mm)

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.052 in (1.3 mm)
Nom. Diameter0.980 in

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)4.45 Ohm/1000ft12.6 Amps per Conductor at 30oC
Ground Wire4.45 Ohm/1000ft (14.6 Ohm/km)19 Amps per Conductor at 25oC

Voltage

Voltage Rating600 V

Mechanical Characteristics

Max. Pull Tension464.1 lbs (210.5 kg)
Bulk Cable Weight425 lbs/1000ft

Temperature

Operating-40°C To +90°C

Bend Radius

Stationary Min.11.76 in (298.7 mm)
Installation Min.11.76 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
CEC / C(UL) ComplianceHL, ACIC.
European Directive ComplianceEU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)