Belden Store
24518D

Product Number: 24518D

ACIC 600V, 4 Tri #18 Str TC, XLPE Ins E1, IS/OS, PVC Jkt, AIA Armor, Blk PVC Jkt, 90C Wet 105C Dry CSA HLBCD SUN RES -40C

Canadian Instrumentation Cable TC-ACIC 600V, 4 Triad 18AWG (7x26) Tinned Copper, XLPE Insulation E1 Color Code, Individual & Overall Beldfoil® Shield, PVC Inner Jacket, Aluminum Interlock Armor, Black PVC Outer Jacket, 90C Wet 105C Dry CSA HLBCD SUN RES -40C

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners

Construction Details

Conductor

ElementTriad(s)
No. of Elements12
Size18 AWG
Stranding7x26
MaterialTC - Tinned Copper

Insulation

ElementTriad(s)
MaterialXLP, XLPO, XLPE (Thermoset)
Nom. Thickness0.031 in (0.79 mm)
Nom. Insulation Diameter0.160 in (4.06 mm)
Color CodeBlack & Red & White Numbered 1, Black & Red & White Numbered 2, Black & Red & White Numbered 3, Black & Red & White Numbered 4

Inner Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type20 AWG (7x28) TC

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type18 AWG (7x26) TC

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.063 in (1.6 mm)
Nom. Diameter0.617 in (15.7 mm)
ColorBlack

Armor

Armor Type & MaterialAIA - Aluminum Interlock Armor

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.052 in (1.3 mm)
Nom. Diameter0.946 in (24.0 mm)

Electrical Characteristics

Electricals

Nom. Conductor DCR7.4 Ohm/1000ft
Nom. Inner Shield DCR8.1 Ohm/1000ft (27 Ohm/km)
Max. Current7 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V RMS

Mechanical Characteristics

Max. Pull Tension504 lbs (229 kg)
Bulk Cable Weight379 lbs/1000ft

Temperature

UL Temperature105°C Dry, 90°C Wet
Operating-40°C To +105°C

Bend Radius

Stationary Min.11.35 in (288.3 mm)
Installation Min.11.35 in (288.3 mm)

Standards and Compliance

Environmental SuitabilityIndoor/Outdoor, Indoor, Outdoor, Sunlight Resistance, UV Resistance
Flammability / Reaction to FireFT4
AWM ComplianceC22.2 #239 Type ACIC, C22.2 #174 HL BCD
CEC / C(UL) ComplianceACIC, LL7874.
APAC ComplianceChina RoHS II (GB/T 26572-2011)