Belden Store
24514D

Product Number: 24514D

ACIC 600V, 8 Pr #18 Str TC, XLPE Ins E1, IS/OS, PVC Jkt, AIA Armor, Blk PVC Jkt, 90C Wet 105C Dry CSA HLABCD SUN RES -40C

Canadian Instrumentation Cable TC-ACIC 600V, 8 Pair 18AWG (7x26) Tinned Copper, XLPE Insulation E1 Color Code, Individual & Overall Beldfoil® Shield, PVC Inner Jacket, Aluminum Interlock Armor, Black PVC Outer Jacket, 90C Wet 105C Dry CSA HLABCD SUN RES -40C

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.57 Revision Date: 02-25-2026

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners

Construction Details

Overall Cable Diameter (Nominal)1.149 in

Conductor

ElementPair(s)
No. of Elements8
Size18 AWG
Stranding7x26H
MaterialTC - Tinned Copper

Insulation

ElementPair(s)
MaterialXLP, XLPO, XLPE (Thermoset)
Nom. Thickness0.030 in (0.76 mm)
Nom. Insulation Diameter0.106 in mm
Color CodeBlack & White and Numbered

Inner Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type20 AWG (7x28) TC

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type18 AWG (7x26) TC

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.063 in (1.6 mm)
Nom. Diameter0.785 in (19.9 mm)
RipcordYes
ColorBlack

Armor

Armor Type & MaterialAIA - Aluminum Interlock Armor
Armor Thickness1.045 in (26.54 mm)
Diameter Over Armor1.050 in (26.67 mm)

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.052 in (1.3 mm)
Nom. Diameter1.149 in
RipcordYes

Electrical Characteristics

Electricals

Nom. Conductor DCR7.4 Ohm/1000ft
Nom. Inner Shield DCR8.28 Ohm/1000ft (27.2 Ohm/km)
Max. Current9 Amps per Conductor at 30oC

Voltage

Voltage Rating600 V

Mechanical Characteristics

Max. Pull Tension593 lbs (269 kg)
Bulk Cable Weight535 lbs/1000ft

Temperature

Operating-40°C To +90°C Wet/105°C Dry

Bend Radius

Stationary Min.13.788 in (350.22 mm)
Installation Min.13.788 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance
CEC / C(UL) ComplianceACIC, HLABCD.
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.57 Revision Date: 02-25-2026

Resources

Related acic cable