Belden Store
24505D

Product Number: 24505D

ACIC 600V, 2 Pr #16 Str TC, XLPE Ins E1, IS/OS, PVC Jkt, AIA Armor, PVC Jkt, 90C Wet 105C Dry CSA HLABCD SUN RES -40C

Canadian Instrumentation Cable TC-ACIC 600V, 2 Pair 16AWG (7x24) Tinned Copper, XLPE Insulation E1 Color Code, Individual & Overall Beldfoil® Shield, PVC Inner Jacket, Aluminum Interlock Armor, PVC Outer Jacket, 90C Wet 105C Dry CSA HLABCD SUN RES -40C

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

24505D is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeOrder
24505D 0602460ReelOrder online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.186 Revision Date: 02-27-2026

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners

Construction Details

Overall Cable Diameter (Nominal)0.911 in

Conductor

ElementPair(s)
No. of Elements2
Size16 AWG
Stranding7x24
MaterialTC - Tinned Copper

Insulation

ElementPair(s)
MaterialXLP, XLPO, XLPE (Thermoset)
Nom. Thickness0.030 in (0.76 mm)
Nom. Insulation Diameter0.118 in mm
Color CodeBlack, White

Inner Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type18 AWG (7x26) TC

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type16 AWG (7x24) TC

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.063 in (1.6 mm)
Nom. Diameter0.582 in (14.8 mm)
RipcordYes
ColorBlack

Armor

Armor Type & MaterialAIA - Aluminum Interlock Armor
Armor Thickness0.807 in (20.5 mm)
Diameter Over Armor0.812 in (20.6 mm)

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.052 in (1.3 mm)
Nom. Diameter0.911 in

Electrical Characteristics

Electricals

Nom. Conductor DCR4.6 Ohm/1000ft
Nom. Inner Shield DCR5.47 Ohm/1000ft (17.9 Ohm/km)
Max. Current15.2 Amps per Conductor at 30oC

Voltage

Voltage Rating600 V

Mechanical Characteristics

Max. Pull Tension401 lbs (182 kg)
Bulk Cable Weight315 lbs/1000ft

Temperature

Operating-40°C To +90°C Wet/105°C Dry

Bend Radius

Stationary Min.10.932 in (277.67 mm)
Installation Min.10.932 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance
CEC / C(UL) ComplianceACIC, HLABCD.
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.186 Revision Date: 02-27-2026

Resources

Related acic cable