Belden Store
23568D

Product Number: 23568D

ACIC 300V, 36 Pr #16 Str TC, XLPE Ins E1, IS/OS, PVC Jkt, AIA Armor, PVC Jkt, 90C Dry/Wet CSA HLABCD SUN RES -40C

Canadian Instrumentation Cable TC-ACIC 300V, 36 Pair 16AWG (7x24) Tinned Copper, XLPE Insulation E1 Color Code, Individual & Overall Beldfoil® Shield, PVC Inner Jacket, Aluminum Interlock Armor, PVC Outer Jacket, 90C Dry/Wet CSA HLABCD SUN RES -40C

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.98 Revision Date: 03-26-2026

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners

Physical Characteristics (Overall)

Conductor Count72

Conductor

ElementConductor(s)
AWG16
Stranding7x24
MaterialTC - Tinned Copper
No. of Pairs36

Insulation

ElementPair(s)
MaterialXLP, XLPO, XLPE (Thermoset)
Nominal Diameter0.090 in
Nominal Wall Thickness0.025 in

Inner Shield

TypeTape
MaterialBi-Laminate (Alum+Poly)
Material Trade NameBeldfoil®
Coverage [%]100%
Drainwire MaterialTC - Tinned Copper
Drainwire AWG18

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nominal Diameter1.57 in

Outer Shield

TypeTape
MaterialBi-Laminate (Alum+Poly)
Material Trade NameBeldfoil®
Coverage [%]100%
Drainwire MaterialTC - Tinned Copper
Drainwire AWG16

Outer Jacket

MaterialPVC - Polyvinyl Chloride

Construction and Dimensions

Armor

Type of ArmorInterlocked
MaterialAluminum

Electrical Characteristics

Conductor DCR

Nominal Conductor DCR4.2 ohm/1000ft

Current

Max. Recommended Current [A]10 Amps per Conductor at 30oC

Voltage

UL Voltage Rating300 V

Temperature Range

Operating Temperature Range-40°C To +105°C

Mechanical Characteristics

Bulk Cable Weight1978 lbs/1000ft
Maximum Recommended Pulling Tension771 lbs
Minimum Bend Radius During Installation23.7 in

Standards

CEC/C(UL) ComplianceACIC
CSA AWM ComplianceC22.2 #239 Type ACIC, C22.2 #174 HL BCD

Suitability

Suitability - IndoorYes
Suitability - OutdoorYes
Suitability - Sunlight ResistanceYes

Flammability, LS0H, Toxicity Testing

CSA/C(UL) FlammabilityFT4

History

Update and RevisionRevision Number: 0.98 Revision Date: 03-26-2026

Resources