Belden Store
23538D

Product Number: 23538D

ACIC 300V, 24 Pr #16 Str TC, XLPE Ins E1, IS/OS, PVC Jkt, AIA Armor, PVC Jkt, 90C Wet 105C Dry CSA HLABCD SUN RES -40C

Canadian Instrumentation Cable TC-ACIC 300V, 24 Pair 16AWG (7x24) Tinned Copper, XLPE Insulation E1 Color Code, Individual & Overall Beldfoil® Shield, PVC Inner Jacket, Aluminum Interlock Armor, PVC Outer Jacket, 90C Wet 105C Dry CSA HLABCD SUN RES -40C

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.57 Revision Date: 03-11-2026

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners

Construction Details

Overall Cable Diameter (Nominal)1.760 in

Conductor

ElementPair(s)
No. of Elements24
Size16 AWG
Stranding7x24
MaterialTC - Tinned Copper

Insulation

ElementPair(s)
MaterialXLP, XLPO, XLPE (Thermoset)
Nom. Thickness0.025 in (0.64 mm)
Nom. Insulation Diameter0.108 in mm
Color CodeBlack & White and Numbered

Inner Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type18 AWG (7x26) TC

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type18 AWG (7x24) TC

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.083 in (2.1 mm)
Nom. Diameter1.376 in (34.95 mm)
RipcordYes
ColorBlack

Armor

Armor Type & MaterialAIA - Aluminum Interlock Armor
Armor Thickness1.636 in (41.55 mm)
Diameter Over Armor1.641 in (41.68 mm)

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.062 in (1.6 mm)
Nom. Diameter1.760 in

Electrical Characteristics

Electricals

Nom. Conductor DCR4.6 Ohm/1000ft
Nom. Inner Shield DCR5.47 Ohm/1000ft (17.9 Ohm/km)
Max. Current7.5 Amps per Conductor at 30oC

Voltage

Voltage Rating300 V

Mechanical Characteristics

Max. Pull Tension1972 lbs (894.5 kg)
Bulk Cable Weight1397 lbs/1000 ft

Temperature

Operating-40°C To +90°C Wet/105°C Dry

Bend Radius

Stationary Min.21.12 in (536.4 mm)
Installation Min.21.12 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance
CEC / C(UL) ComplianceACIC, HLABCD.
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.57 Revision Date: 03-11-2026

Resources

Related acic cable