Belden Store
23525D

Product Number: 23525D

ACIC 300V, 12 Pr #16 Str TC, XLPE Ins E1, IS/OS, PVC Jkt, AIA Armor, PVC Jkt, 90C Wet 105C Dry CSA HLABCD SUN RES -40C

Canadian Instrumentation Cable TC-ACIC 300V, 12 Pair 16AWG (7x24) Tinned Copper, XLPE Insulation E1 Color Code, Individual & Overall Beldfoil® Shield, PVC Inner Jacket, Aluminum Interlock Armor, PVC Outer Jacket, 90C Wet 105C Dry CSA HLABCD SUN RES -40C

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.111 Revision Date: 03-12-2026

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners

Construction Details

Overall Cable Diameter (Nominal)1.370 in (34.80 mm)

Conductor

ElementPair(s)
No. of Elements12
Size16 AWG
Stranding7x24
MaterialTC - Tinned Copper

Insulation

ElementPair(s)
MaterialXLP, XLPO, XLPE (Thermoset)
Nom. Thickness0.025 in (0.64 mm)
Nom. Insulation Diameter0.108 in mm
Color CodeBlack, White and Numbered

Inner Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type16 AWG (7x24) TC

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type18 AWG (7x26) TC

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.083 in (2.1 mm)
Nom. Diameter1.006 in (25.55 mm)
ColorBlack

Armor

Armor Type & MaterialAIA - Aluminum Interlock Armor
Armor Thickness1.266 in (32.16 mm)
Diameter Over Armor1.271 in (32.28 mm)

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.052 in (1.3 mm)
Nom. Diameter1.370 in (34.80 mm)
RipcordYes

Electrical Characteristics

Electricals

Nom. Conductor DCR4.6 Ohm/1000ft
Nom. Inner Shield DCR2.98 Ohm/1000ft (9.78 Ohm/km)
Max. Current3.2 Amps per Conductor at 30oC

Voltage

Voltage Rating300 V

Mechanical Characteristics

Max. Pull Tension1114.9 lbs (505.71 kg)
Bulk Cable Weight843 lbs/1000ft

Temperature

Operating-40°C To +105°C Dry/90°C Wet

Bend Radius

Stationary Min.16.44 in (417.6 mm)
Installation Min.16.44 in (417.6 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance
CEC / C(UL) ComplianceHLABCD.

History

Update and RevisionRevision Number: 0.111 Revision Date: 03-12-2026

Resources