Belden Store
23522D

Product Number: 23522D

ACIC 300V, 2 Tri #16 Str TC, XLPE Ins E1, IS/OS, PVC Jkt, AIA Armor, PVC Jkt, 90C Dry/Wet CSA HLBCD SUN RES -40C

Canadian Instrumentation Cable TC-ACIC 300V, 2 Triad 16AWG (7x24) Tinned Copper, XLPE Insulation E1 Color Code, Individual & Overall Beldfoil® Shield, PVC Inner Jacket, Aluminum Interlock Armor, PVC Outer Jacket, 90C Dry/Wet CSA HLBCD SUN RES -40C

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.277 Revision Date: 03-13-2026

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners

Construction Details

Overall Cable Diameter (Nominal)0.925 in

Conductor

ElementTriad(s)
No. of Elements2
Size16 AWG
Stranding7x24
MaterialTC - Tinned Copper

Insulation

ElementTriad(s)
MaterialXLP, XLPO, XLPE (Thermoset)
Nom. Thickness0.025 in (0.64 mm)
Nom. Insulation Diameter0.108 in mm
Color CodeBlack & White & Red and numbered

Inner Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type18 AWG (7x26.5) TC

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.063 in (1.6 mm)
Nom. Diameter0.0596 in (1.51 mm)
RipcordYes
ColorBlack

Armor

Armor Type & MaterialAIA - Aluminum Interlock Armor
Armor Thickness0.821 in (20.9 mm)
Diameter Over Armor0.826 in (21.0 mm)

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.052 in (1.3 mm)
Nom. Diameter0.925 in

Electrical Characteristics

Electricals

Nom. Conductor DCR4.6 Ohm/1000ft
Nom. Inner Shield DCR5.47 Ohm/1000ft (17.9 Ohm/km)
Max. Current13.3 Amps per Conductor at 30oC

Voltage

Voltage Rating300 V

Mechanical Characteristics

Max. Pull Tension472 lbs (214 kg)
Bulk Cable Weight343 lbs/1000ft

Temperature

Operating-40°C To +90°C

Bend Radius

Stationary Min.11.1 in (282 mm)
Installation Min.11.1 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance
CEC / C(UL) ComplianceACIC, HLBCD.
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.277 Revision Date: 03-13-2026

Resources

Related acic cable