Belden Store
23520D

Product Number: 23520D

ACIC 300V, 4 Tri #16 Str TC, XLPE Ins E1, IS/OS, PVC Jkt, AIA Armor, PVC Jkt, 90C Dry/Wet CSA HLBCD SUN RES -40C

Canadian Instrumentation Cable TC-ACIC 300V, 4 Triad 16AWG (7x24) Tinned Copper, XLPE Insulation E1 Color Code, Individual & Overall Beldfoil® Shield, PVC Inner Jacket, Aluminum Interlock Armor, PVC Outer Jacket, 90C Dry/Wet CSA HLBCD SUN RES -40C

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.57 Revision Date: 03-18-2026

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners

Construction Details

Overall Cable Diameter (Nominal)1.019 in

Conductor

ElementTriad(s)
No. of Elements4
Size16 AWG
Stranding7x24
MaterialTC - Tinned Copper

Insulation

ElementTriad(s)
MaterialXLP, XLPO, XLPE (Thermoset)
Nom. Thickness0.025 in (0.64 mm)
Nom. Insulation Diameter0.108 in mm
Color CodeBlack, White & Red and Numbered

Inner Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type16 AWG (7x24) TC

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type18 AWG (7x26) TC

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.063 in (1.6 mm)
Nom. Diameter0.690 in (17.5 mm)
RipcordYes
ColorBlack

Armor

Armor Type & MaterialAIA - Aluminum Interlock Armor
Armor Thickness0.915 in (23.2 mm)
Diameter Over Armor0.920 in (23.4 mm)

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.052 in (1.3 mm)
Nom. Diameter1.019 in
RipcordYes

Electrical Characteristics

Electricals

Nom. Conductor DCR4.6 Ohm/1000ft
Nom. Inner Shield DCR3.26 Ohm/1000ft (10.7 Ohm/km)
Max. Current4.48 Amps per Conductor at 30oC

Voltage

Voltage Rating300 V

Mechanical Characteristics

Max. Pull Tension686.5 lbs (311.4 kg)
Bulk Cable Weight457 lbs/1000ft

Temperature

Operating-40°C To +105°C Dry/90°C Wet

Bend Radius

Stationary Min.12.228 in (310.59 mm)
Installation Min.12.228 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance
CEC / C(UL) ComplianceACIC, HLBCD.
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.57 Revision Date: 03-18-2026

Resources

Related acic cable