ACIC 300V, 4 Tri #18 Str TC, XLPE Ins E1, IS/OS, PVC Jkt, AIA Armor, PVC Jkt, 90C Wet 105C Dry CSA HLBCD SUN RES -40C

Canadian Instrumentation Cable TC-ACIC 300V, 4 Triad 18AWG (7x26) Tinned Copper, XLPE Insulation E1 Color Code, Individual & Overall Beldfoil® Shield, PVC Inner Jacket, Aluminum Interlock Armor, PVC Outer Jacket, 90C Wet 105C Dry CSA HLBCD SUN RES -40C

Availability
Global
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

23515D is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Put-Up TypeUPCOrder
23515D 06010000Reel612825322764Order online
23515D 0605000Reel612825322795Order online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.65 Revision Date: 05-04-2026

Product Overview

Suitable ApplicationsIndustrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners

Physical Characteristics (Overall)

Conductor Count12

Conductor

ElementTriad(s)
AWG18
Stranding7x26
MaterialTC - Tinned Copper
No. of Triads4

Insulation

ElementTriad(s)
MaterialXLP, XLPO, XLPE (Thermoset)
Nominal Diameter0.093 in
Nominal Wall Thickness0.026 in

Color Chart

Color
Black & Red & White Numbered 1
Black & Red & White Numbered 2
Black & Red & White Numbered 3
Black & Red & White Numbered 4

Inner Shield

TypeTape
MaterialBi-Laminate (Alum+Poly)
Material Trade NameBeldfoil®
Coverage [%]100%
Drainwire MaterialTC - Tinned Copper
Drainwire AWG20

Inner Jacket

MaterialPVC - Polyvinyl Chloride
ColorBlack
Nominal Diameter0.630 in
Nominal Wall Thickness0.063 in

Outer Shield

TypeTape
MaterialBi-Laminate (Alum+Poly)
Material Trade NameBeldfoil®
Coverage [%]100%
Drainwire MaterialTC - Tinned Copper
Drainwire AWG18

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nominal Diameter0.959 in
Nominal Wall Thickness0.052 in

Construction and Dimensions

Armor

Type of ArmorInterlocked
MaterialAluminum

Electrical Characteristics

Conductor DCR

Nominal Conductor DCR7.4 Ohm/1000ft
Nominal Inner Shield DCR8.3 Ohm/1000ft
Nominal Outer Shield DCR4.71 Ohm/1000ft

Current

Max. Recommended Current [A]7 Amps per Conductor at 30oC

Voltage

UL Voltage Rating300 V RMS

Temperature Range

UL Temperature Rating105°C Dry, 90°C Wet
Operating Temperature Range-40°C To +105°C

Mechanical Characteristics

UV ResistanceYes
Bulk Cable Weight375 lbs/1000ft
Maximum Recommended Pulling Tension504 lbs
Minimum Bend Radius During Installation11.51 in

Standards

CEC/C(UL) ComplianceACIC
CSA AWM ComplianceC22.2 #239 Type ACIC, C22.2 #174 HL BCD
CSA TypeCSA C22.2 #239,CSA C22.2 #174

Applicable Environmental and Other Programs

Environmental SpaceIndoor/Outdoor

Suitability

Suitability - IndoorYes
Suitability - OutdoorYes
Suitability - Sunlight ResistanceYes

Flammability, LS0H, Toxicity Testing

CSA/C(UL) FlammabilityFT4

History

Update and RevisionRevision Number: 0.65 Revision Date: 05-04-2026