Belden Store
SPE101

Product Number: SPE101

Datatuff Ind SPE 10Mbps 18AWG SF/UTP PVC

Datatuff Ind SPE 10Mbps 18AWG PE SF/UTP PVC

Availability
Americas
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

SPE101 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Order
SPE101 0061000Order online
SPE101 0101000Order online

Specifications

Product Overview

Suitable Applicationsdata communications, cameras, PLCs, switches, outdoor, indoor etc.

Construction Details

Overall Cable Diameter (Nominal).311 in (7.90 mm)

Conductor

Size18 AWG
StrandingSolid
MaterialTC - Tinned Copper
No. of Pairs1

Insulation

MaterialPE - Polyethylene (Foam)
Nom. Insulation Diameter0.098 in (2.5 mm)
Color CodeWhite & Blue

Outer Shield

Shield TypeMaterialCoverage
TapeBi-Laminate (Alum+Poly)100%
BraidTinned Copper (TC)90%

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Diameter0.311 in (7.90 mm)

Electrical Characteristics

Electricals

Max. Conductor DCR23 Ohm/km (7.0 Ohm/1000ft)
Max. Mutual Capacitance56 pF/m (17 pF/ft)
Max. Capacitance Unbalance330 pF/100m

Delay

Frequency100 MHz
Max. Delay450 ns/100m
Nom. Velocity of Prop.76%

High Frequency

Frequency [MHz]Max. Insertion Loss (Attenuation)Min. RL (Return Loss) [dB]Min. PSANEXT [dB]Min. Coupling Attenuation [dB]Nom. Characteristic Impedance [Ohm]
0.11.0 dB/100m11.56750100
0.51.2 dB/100m1564.750100
0.7721.3 dB/100m1561.550100
11.4 dB/100m1561.450100
21.9 dB/100m1554.550100
42.6 dB/100m1549.450100
83.6 dB/100m1544.350100
105.9 dB/100m1542.650100
165.1 dB/100m1539.150100
205.7 dB/100m1537.550100

Voltage

UL Voltage Rating300 V (UL 13 PLTC)

Mechanical Characteristics

Max. Pull Tension25 lbs (11 kg)
Bulk Cable Weight56 lbs/1000ft

Temperature

UL Temperature75°C
Operating-30°C To +75°C

Bend Radius

Installation Min.2.4 in (61 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance, Oil Resistance
Flammability / Reaction to FireUL 1685 UL Loading
NEC / UL ComplianceCM, PLTC
IEEE ComplianceIEEE 802.3cg
TIA/EIA ComplianceANSI/TIA-568.5
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), REACH, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE), REACH: 2022-04-27
APAC ComplianceChina RoHS II (GB/T 26572-2011)

Product Notes

NotesElectrical values are expected performance based on cable testing and representative performance within a typical Belden system.

History

Update and RevisionRevision Number: 0.47 Revision Date: 02-20-2026

Resources

Related industrial ethernet cable