Belden Store
Belden133082A

Product Number: 133082A

DeviceBus®, 2 Pr #15+18 Str TC, PVC+FPE Ins, IS+OA TC Brd, PVC Jkt, SIA Armor, PVC Jkt, CM PLTC

DeviceBus® for ODVA DeviceNetTM, 2 Pair 15+18AWG (19x27+19x30) Tinned Copper, PVC+Foam PE Insulation, Individual Beldfoil® & OA Tinned Copper Braid(65%) Shield, PVC Inner Jacket, Steel Interlock Armor, PVC Outer Jacket, CM PLTC

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Suitable Applicationsexposure to rodent, crush, or cut through force, harsh environment, ODVA device-level communication, used with CIP (common Industrial Protocol) for control, configuration, and data collection between devices, such as sensors and actuators, and higher level devices such as PLC, and PC in industrial automation, bus topology, etc.

Construction Details

Overall Cable Diameter (Nominal)0.770 in (19.6 mm)

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Power Pair(s)115 AWG19x27TC - Tinned Copper
Data Pair(s)118 AWG19x30TC - Tinned Copper

Insulation

ElementMaterialNom. ThicknessColor CodeNotes
Power Pair(s)PVC - Polyvinyl Chloride0.021 in (0.53 mm)Red & Black
Data Pair(s)PE - Polyethylene (Foam)0.053 in (1.3 mm)Blue & WhiteHDPE

Inner Shield

ElementShield TypeMaterialCoverage
Power Pair(s)TapeBi-Laminate (Alum+Poly)100%
Data Pair(s)TapeBi-Laminate (Alum+Poly)100%

Outer Shield

Shield TypeBraid
MaterialTinned Copper (TC)
Coverage65%
Drainwire Type18 AWG (19x30) TC

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.060 in (1.5 mm)
Nom. Diameter0.480 in (12.2 mm)

Armor

Armor Type & MaterialSIA - Steel Interlock Armor

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.050 in (1.3 mm)
Nom. Diameter0.770 in (19.6 mm)

Electrical Characteristics

Nom Outer Shield DCR1.8 Ohm/1000ft (5.9 Ohm/km)

Electricals

ElementNom. Conductor DCRNom. Capacitance Cond-to-CondNom. Characteristic ImpedenceNom. Velocity of Prop.Max. Current
Power Pair(s)3.6 Ohm/1000ft (12 Ohm/km)8 Amps per Conductor
Data Pair(s)6.9 Ohm/1000ft (23 Ohm/km)12 pF/ft (39 pF/m)120 Ohm75%5 Amps per Conductor

High Frequency

ElementFrequency [MHz]Max. Insertion Loss (Attenuation)
Data Pair(s)0.1250.13 dB/100ft
0.50.25 dB/100ft
10.36 dB/100ft

Voltage

UL Voltage Rating300 V (CM, PLTC)

Mechanical Characteristics

Max. Pull Tension200 lbs (91 kg)
Bulk Cable Weight498 lbs/1000ft (741 kg/km)

Temperature

UL Temperature75°C
Operating-20°C to +75°C

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance
CPR ComplianceCPR Euroclass: Eca
NEC / UL ComplianceArticle 725, Article 800
CEC / C(UL) ComplianceCMG HLBCD.
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
UK Regulation ComplianceUKCA Mark
APAC ComplianceChina RoHS II (GB/T 26572-2011)

Product Notes

NotesThick. Meter marks on jacket to aid users in installation. ODVA DeviceNet is an Open DeviceNet Vendor Associatio, Inc. Trademark. Jacket printed ""1PR16"" instead of ""1PR15"" due to UL requirements for CMG Listing.

History

Update and RevisionRevision Number: 0.75 Revision Date: 05-05-2023

Resources