Belden Store
Belden133076F

Product Number: 133076F

Fieldbus, 1 Pr #18 Str TC, PP ins, OS, PVC Jkt, SIA Armor, PVC Jkt, ISA/SP-50 Type A, PLTC, CM

Fieldbus, 1 Pair 18AWG (7x26) Tinned Copper, PP insulation, Overall Beldfoil® Shield, PVC Inner Jacket, Steel Interlock Armor, PVC Outer Jacket, ISA/SP-50 Type A, PLTC, CM

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Suitable Applicationsexposure to rodent, crush, or cut through force, harsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature enviornments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.

Construction Details

Overall Cable Diameter (Nominal)0.572 in (14.5 mm)

Conductor

ElementPair(s)
No. of Elements1
Size18 AWG
Stranding7x26
MaterialTC - Tinned Copper

Insulation

ElementPair(s)
MaterialPP - Polypropylene
Nom. Thickness0.022 in (0.56 mm)
Color CodeBlue & Orange

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type20 AWG (7x28) TC

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Diameter0.280 in (7.11 mm)

Armor

Armor Type & MaterialSIA - Steel Interlock Armor

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.045 in (1.1 mm)
Nom. Diameter0.572 in (14.5 mm)

Electrical Characteristics

Nom Outer Shield DCR7.5 Ohm/1000ft (25 Ohm/km)

Electricals

ElementPair(s)
Nom. Conductor DCR5.86 Ohm/1000ft (19.2 Ohm/km)
Nom. Capacitance Cond-to-Shield45 pF/ft
Nom. Characteristic Impedence100 Ohm
Nom. Velocity of Prop.66%
Max. Current5.2 Amps per Conductor

High Frequency (Nominal/Typical)

ElementPair(s)
Frequency [MHz]0.039
Nom. Insertion Loss (Attenuation)0.08 dB/100ft

High Frequency

Frequency [MHz]0.031
Max. Insertion Loss (Attenuation)0.091 dB/100ft

Voltage

UL Voltage Rating300 V (CM, PLTC)

Mechanical Characteristics

Max. Pull Tension200 lbs (91 kg)
Bulk Cable Weight288 lbs/1000ft (429 kg/km)

Temperature

UL Temperature105°C
Operating-40°C to +105°C

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance
CPR ComplianceCPR Euroclass: Eca
NEC / UL ComplianceArticle 725, Article 800
CEC / C(UL) ComplianceCMG HLBCD.
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
UK Regulation ComplianceUKCA Mark
Other Standard Compliance(s)ISA/SP-50 Type A

Product Notes

NotesFieldbus: Orange jacket. Profibus PA: Intrinsically Safe Blue jacket. Jacket diameter tolerance: +/- .010

History

Update and RevisionRevision Number: 0.74 Revision Date: 05-05-2023

Resources

Related industrial ethernet cable