Belden Store
2118Z

Product Number: 2118Z

Fieldbus, 1 Pr #18 Str TC, XLPO Ins, OS, LSZH-TS Jkt, 600V TC

Fieldbus, 1 Pair 18AWG (7x26) Tinned Copper, XLPO Insulation, Overall Beldfoil® Shield, LSZH-TS Outer Jacket, 600V TC

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

2118Z is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorUPCOrder
2118Z 0105000Black612825129509Order online

Specifications

Product Overview

Suitable Applicationsharsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc.

Construction Details

Conductor

ElementPair(s)
No. of Elements1
Size18
Stranding7x26
MaterialTC - Tinned Copper

Insulation

MaterialXLPE - Cross-Linked Polyethylene (Thermoset)
Nom. Thickness0.032 in (0.81 mm)
Nom. Insulation Diameter0.110 in (2.79 mm)
Color CodeBlue & Orange

Inner Shield

ElementData Pair(s)

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%

Outer Jacket

MaterialLSZH - Low Smoke Zero Halogen (Flame Retardant, Thermoset)
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.348 in

Electrical Characteristics

Electricals

Nom. Conductor DCR5.86 Ohm/1000ft (19.2 Ohm/km)
Nom. Capacitance Cond-to-Cond22.0 pF/ft (72.2 pF/m)
Nom. Inductance0.22 μH/ft (0.72 μH/m)
Nom. Velocity of Prop.64%

High Frequency (Nominal/Typical)

Frequency [kHz]39
Nom. Insertion Loss (Attenuation) [dB/100ft]0.08

Voltage

UL Voltage Rating600 V (TC), 1000 V RMS (UL1309)

Mechanical Characteristics

Max. Pull Tension57 lbs (26 kg)
Bulk Cable Weight56 lbs/1000ft (83 kg/km)

Temperature

UL Temperature90°C Wet/Dry
Operating-40°C to +90°C
Installation-25°C To +90°C

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance
Flammability / Reaction to Fire1202, IEEE 383 Vertical Tray Flame Test (70,000 BTU)
CPR ComplianceCPR Euroclass: Fca
NEC / UL ComplianceTC
CEC / C(UL) ComplianceFT4.
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

Product Notes

NotesImpedance 100 Ohm @ 31.25 kHz

History

Update and RevisionRevision Number: 0.229 Revision Date: 02-20-2026