DeviceBus®, 2 Pr #16+18 Str TC, PVC-NYL+PP Ins, IS+OA TC Brd, PVC Jkt, AIA Armor, PVC Jkt, CMG CSA HL

DeviceBus® for ODVA DeviceNetTM, 2 Pair 16+18AWG (19x29+19x30) Tinned Copper, PVC-NYL+PP Insulation, Individual Beldfoil® & OA Tinned Copper Braid(65%) Shield, PVC Inner Jacket, Aluminum Interlock Armor, PVC Outer Jacket, CMG CSA HL

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Suitable Applicationsexposure to rodent, crush, or cut through force, harsh environment, ODVA device-level communication, used with CIP (common Industrial Protocol) for control, configuration, and data collection between devices, such as sensors and actuators, and higher level devices such as PLC, and PC in industrial automation, bus topology, etc.

Construction Details

Overall Cable Diameter (Nominal)0.818 in (20.8 mm)

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Power Pair(s)116 AWG19x29TC - Tinned Copper
Data Pair(s)118 AWG19x30TC - Tinned Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor CodeNotes
Power Pair(s)PVC/Nylon - Polyvinyl Chloride + Nylon0.022 in (0.56 mm)0.101 in (2.57 mm)Red & Black
Data Pair(s)PP - Polypropylene0.068 in (1.7 mm)0.116 in (2.95 mm)Blue & WhiteFlame Retardant

Inner Shield

ElementShield TypeMaterialCoverage
Power Pair(s)TapeBi-Laminate (Alum+Poly)100%
Data Pair(s)TapeBi-Laminate (Alum+Poly)100%

Outer Shield

Shield TypeBraid
MaterialTinned Copper (TC)
Coverage65%
Drainwire Type16 AWG (19x29) TC

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.060 in (1.5 mm)
Nom. Diameter0.525 in (13.3 mm)

Armor

Armor Type & MaterialAIA - Aluminum Interlock Armor

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.050 in (1.3 mm)
Nom. Diameter0.818 in (20.8 mm)

Electrical Characteristics

Electricals

ElementNom. Conductor DCRNom. Inner Shield DCRNom. Capacitance Cond-to-CondNom. Characteristic ImpedenceNom. Velocity of Prop.
Power Pair(s)4.9 Ohm/1000ft (16 Ohm/km)1.8 Ohm/1000ft (5.9 Ohm/km)
Data Pair(s)6.9 Ohm/1000ft (23 Ohm/km)14.7 pF/ft (48.2 pF/m)120 Ohm75%

High Frequency

ElementData Pair(s)

Voltage

Voltage Rating(300 V)

Mechanical Characteristics

Max. Pull Tension200 lbs (91 kg)
Bulk Cable Weight136 lbs/1000ft (202 kg/km)

Temperature

UL Temperature75°C
Operating-40°C to +75°C

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance
SustainabilityCA Prop 65
Flammability / Reaction to FireFT4
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)