Teck90 1000V, 6+G C #10+12 Str BC, XLPE Ins M4, PVC Jkt, AIA Armor, Blk PVC Jkt, CSA HL SUN RES -40C
Teck90 1000V, 6+G Conductor 10+12AWG (7x18) Bare Copper, XLPE Insulation M4 Color Code, PVC Inner Jacket, Aluminum Interlock Armor, Black PVC Outer Jacket, CSA HL SUN RES -40C
- Availability
- Global
- Status
- Active
Specifications
Information
| Put-Up Type | Reel |
|---|---|
| Update and Revision | Revision Number: 0.45 Revision Date: 03-23-2026 |
Product Overview
| Suitable Applications | CEC Power and Control Applications up to 600V |
|---|
Physical Characteristics (Overall)
| Conductor Count | 6 |
|---|
Conductor
| Element | AWG | Stranding | Material | No. of Conductors |
|---|---|---|---|---|
| Conductor(s) | 10 | 7x18 | BC - Bare Copper | 6 |
| Ground | 12 | 7x20 | BC - Bare Copper | 1 |
Insulation
| Element | Material | Nominal Diameter | Nominal Wall Thickness |
|---|---|---|---|
| XLP, XLPO, XLPE (Thermoset) | 0.180 in mm | 0.045 in | |
| Ground Wire | No Insulation |
Color Chart
| Color | Black |
|---|
Inner Jacket
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nominal Diameter | 0.738 in |
Outer Jacket
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nominal Diameter | 1.061 in |
| Nominal Wall Thickness | 0.048 in |
| Ripcord | Yes |
Construction and Dimensions
Armor
| Type of Armor | Interlocked |
|---|---|
| Material | Aluminum |
Electrical Characteristics
Conductor DCR
| Nominal Conductor DCR | 1.03 ohms/1000ft |
|---|
Current
| Max. Recommended Current [A] | 30 Amps per Conductor at 30oC |
|---|
Voltage
| Non-UL Description | TECK 90 |
|---|
Temperature Range
| Non-UL Temp Rating | 90°C |
|---|---|
| Operating Temperature Range | -40°C To +90°C |
Mechanical Characteristics
| Bulk Cable Weight | 553 lbs/1000ft |
|---|---|
| Maximum Recommended Pulling Tension | 200 lbs |
| Minimum Bend Radius During Installation | 12.7 in |
Applicable Environmental and Other Programs
| EU Directive 2000/53/EC (ELV) | Yes |
|---|---|
| EU Directive 2011/65/EU (RoHS 2) | Yes |
| EU Directive 2012/19/EU (WEEE) | Yes |
| EU Directive 2015/863/EU (RoHS 2 amendment) | Yes |
| EU Directive Compliance | EU Directive 2003/11/EC (BFR) |
| EU CE Mark | Yes |
Suitability
| Suitability - Burial | Yes |
|---|---|
| Suitability - Hazardous Locations | Yes |
| Suitability - Indoor | Yes |
| Suitability - Outdoor | Yes |
| Suitability - Sunlight Resistance | Yes |
History
| Update and Revision | Revision Number: 0.45 Revision Date: 03-23-2026 |
|---|
Resources
Related control cable

1285
RW90 1000V, 4 Str BC, XLPE Ins, 90C Dry/Wet CSA HL SUN RES
1 · BC - Bare Copper · XLP, XLPO, XLPE (Thermoset) · PVC - Polyvinyl Chloride

19105
Portable Cordage, 3 C #10 Str BC, EPDM Ins, Rubber Jkt, UL Type S
3 · 10 AWG · BC - Bare Copper · EPDM - Ethylene Propylene Diene Monomer
1 item

19106
Portable Cordage, 3 C #12 Str BC, EPDM Ins, Rubber Jkt, UL Type S
3 · 12 AWG · BC - Bare Copper · EPDM - Ethylene Propylene Diene Monomer
1 item

19107
Portable Cordage, 3 C #14 Str BC, EPDM Ins, Rubber Jkt, UL Type S
3 · 14 AWG · BC - Bare Copper · EPDM - Ethylene Propylene Diene Monomer
1 item