Belden Store
C5734

Product Number: C5734

Teck90 1000V, 6+G C #12+14 Str BC, XLPE Ins M4, PVC Jkt, AIA Armor, Blk PVC Jkt, CSA HL SUN RES -40C

Teck90 1000V, 6+G Conductor 12+14AWG (7x20H) Bare Copper, XLPE Insulation M4 Color Code, PVC Inner Jacket, Aluminum Interlock Armor, Black PVC Outer Jacket, CSA HL SUN RES -40C

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.46 Revision Date: 03-23-2026

Product Overview

Suitable ApplicationsCEC Power and Control Applications up to 600V

Physical Characteristics (Overall)

Conductor Count6

Conductor

ElementAWGStrandingMaterialNo. of Conductors
Conductor(s)127x20.5BC - Bare Copper6
Ground147x22BC - Bare Copper1

Insulation

ElementMaterialNominal DiameterNominal Wall Thickness
XLP, XLPO, XLPE (Thermoset)0.180 in mm0.045 in
Ground WireNo Insulation

Color Chart

ColorBlack

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nominal Diameter0.67 in

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nominal Diameter0.98 in
Nominal Wall Thickness0.048 in
RipcordYes

Construction and Dimensions

Armor

Type of ArmorInterlocked
MaterialAluminum

Electrical Characteristics

Conductor DCR

Nominal Conductor DCR1.62 ohms/1000ft

Current

Max. Recommended Current [A]20 Amps per Conductor at 30oC

Voltage

Non-UL DescriptionTECK 90

Temperature Range

Non-UL Temp Rating90°C
Operating Temperature Range-40°C To +90°C

Mechanical Characteristics

Bulk Cable Weight453 lbs/1000ft
Maximum Recommended Pulling Tension520 lbs
Minimum Bend Radius During Installation11.75 in

Applicable Environmental and Other Programs

EU Directive 2000/53/EC (ELV)Yes
EU Directive 2011/65/EU (RoHS 2)Yes
EU Directive 2012/19/EU (WEEE)Yes
EU Directive 2015/863/EU (RoHS 2 amendment)Yes
EU Directive ComplianceEU Directive 2003/11/EC (BFR)
EU CE MarkYes

Suitability

Suitability - BurialYes
Suitability - Hazardous LocationsYes
Suitability - IndoorYes
Suitability - OutdoorYes
Suitability - Sunlight ResistanceYes