Product Number: C5620

Teck90 1000V, 2+G C #2+6 Str BC, XLPE Ins M4, PVC Jkt, AIA Armor, Blk PVC Jkt, CSA HL SUN RES -40C

Teck90 1000V, 2+G Conductor 2+6AWG (7x10H) Bare Copper, XLPE Insulation M4 Color Code, PVC Inner Jacket, Aluminum Interlock Armor, Black PVC Outer Jacket, CSA HL SUN RES -40C

Availability
Global
Status
Active
Orderable items
4

Ships from and sold by A5 IT.

Part numbers

C5620 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeOrder
C5620 0101640ReelOrder online
C5620 0104920ReelOrder online
C5620 0102500ReelOrder online
C5620 010984ReelOrder online

Specifications

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V

Construction Details

Overall Cable Diameter (Nominal)1.332 in

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Conductor(s)22 AWG7x10BC - Bare Copper
Ground Wire16 AWG7x14BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)XLP, XLPO, XLPE (Thermoset)0.060 in (1.5 mm)0.405 in (10.3 mm)Black, White
Ground WireNo Insulation

Outer Shield

MaterialNo Shield

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.083 in (2.1 mm)
Nom. Diameter0.976 in (24.8 mm)
RipcordYes
ColorBlack

Armor

Armor Type & MaterialAIA - Aluminum Interlock Armor
Armor Thickness0.034 in (0.86 mm)
Diameter Over Armor1.236 in (31.39 mm)

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.048 in (1.2 mm)
Nom. Diameter1.332 in

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)0.16 Ohm/1000ft130 Amps per Conductor at 30oC
Ground Wire0.419 Ohm/1000ft (1.37 Ohm/km)

Voltage

Voltage Rating1000 V (TECK 90)

Mechanical Characteristics

Max. Pull Tension2921.7 lbs (1325.3 kg)
Bulk Cable Weight993 lbs/1000ft

Temperature

UL Temperature90°C
Operating-40°C To +90°C
Installation-25°C To +90°C

Bend Radius

Stationary Min.10.656 in (270.66 mm)
Installation Min.10.656 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance
CEC / C(UL) ComplianceTECK 90, HL.
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)