Belden Store
C5548

Product Number: C5548

Teck90 600V, 20+G C #12+14 Str BC, XLPE Ins M4, PVC Jkt, AIA Armor, Blk PVC Jkt, CSA HL SUN RES -40C

Teck90 600V, 20+G Conductor 12+14AWG (7x20H) Bare Copper, XLPE Insulation M4 Color Code, PVC Inner Jacket, Aluminum Interlock Armor, Black PVC Outer Jacket, CSA HL SUN RES -40C

Availability
Global
Status
Active
Orderable items
3

Ships from and sold by A5 IT.

Part numbers

C5548 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeUPCOrder
C5548 0102500Reel612825282983Order online
C5548 0105000Reel612825282990Order online
C5548 0102952Reel—Order online

Specifications

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V

Construction Details

Overall Cable Diameter (Nominal)1.319 in

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Conductor(s)2012 AWG7x20BC - Bare Copper
Ground Wire114 AWG7x22BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)XLP, XLPO, XLPE (Thermoset)0.030 in (0.76 mm)0.150 in (3.81 mm)Black and Numbered
Ground WireNo Insulation

Outer Shield

MaterialNo Shield

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.083 in (2.1 mm)
Nom. Diameter0.963 in (24.5 mm)
RipcordYes
ColorBlack

Armor

Armor Type & MaterialAIA - Aluminum Interlock Armor
Armor Thickness0.034 in (0.86 mm)
Diameter Over Armor1.223 in (31.06 mm)

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.048 in (1.2 mm)
Nom. Diameter1.319 in
RipcordYes

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)1.7 Ohm/1000ft21 Amps per Conductor at 30oC
Ground Wire2.67 Ohm/1000ft (8.76 Ohm/km)

Voltage

Voltage Rating600 V (TECK 90)

Mechanical Characteristics

Max. Pull Tension1990.6 lbs (902.92 kg)
Bulk Cable Weight978 lbs/1000ft

Temperature

UL Temperature90°C
Operating-40°C To +90°C
Installation-25°C To +90°C

Bend Radius

Stationary Min.10.552 in (268.02 mm)
Installation Min.10.552 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance
CEC / C(UL) ComplianceTECK 90, HL.
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.83 Revision Date: 03-11-2026

Resources

Related control cable