Belden Store
6194

Product Number: 6194

Teck90 600V, 3+4+G C #2+12+6 Str BC, XLPE Ins M4, PVC Jkt, AIA Armor, Blk PVC Jkt, CSA HL SUN RES -40C

Teck90 600V, 3+4+G Conductor 2+12+6AWG (7x10+7x20) Bare Copper, XLPE Insulation M4 Color Code, PVC Inner Jacket, Aluminum Interlock Armor, Black PVC Outer Jacket, CSA HL SUN RES -40C

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.50 Revision Date: 03-20-2026

Physical Characteristics (Overall)

Conductor Count7

Conductor

ElementAWGStrandingMaterialNo. of Conductors
Conductor127x10BC - Bare Copper3
Conductor2127x20BC - Bare Copper4
Ground67x14BC - Bare Copper1

Insulation

ElementMaterialNominal Diameter
Conductor1XLP, XLPO, XLPE (Thermoset)0.405 in
Conductor2XLP, XLPO, XLPE (Thermoset)0.150 in
GroundNo Insulation

Color Chart

Color
Black
Red
Blue

Color Chart 2

Color
Black
Red
Blue
White

Inner Jacket

MaterialPVC - Polyvinyl Chloride
ColorBlack

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nominal Diameter0.873 in

Construction and Dimensions

Armor

Type of ArmorInterlocked
MaterialAluminum

Electrical Characteristics

Conductor DCR

Nominal Conductor DCR0.166 Ohm/1000ft

Current

Max. Recommended Current [A]91 Amps per Conductor at 30oC

Voltage

Non-UL DescriptionTeck90
Non-UL Voltage Rating600 V

Temperature Range

Operating Temperature Range-40°C To +90°C

Mechanical Characteristics

UV ResistanceYes
Bulk Cable Weight1373 lbs/1000ft
Maximum Recommended Pulling Tension6406.9 lbs

Suitability

Suitability - IndoorYes
Suitability - OutdoorYes
Suitability - Sunlight ResistanceYes

Flammability, LS0H, Toxicity Testing

CSA/C(UL) FlammabilityFT4

History

Update and RevisionRevision Number: 0.50 Revision Date: 03-20-2026

Resources