Belden Store
6077

Product Number: 6077

Teck90 600V, 3+G C #12+14 Str BC, XLPE Ins M4, PVC Jkt, SIA Armor, Blk PVC Jkt, CSA HL SUN RES -40C

Teck90 600V, 3+G Conductor 12+14AWG (7x20H) Bare Copper, XLPE Insulation M4 Color Code, PVC Inner Jacket, Steel Interlock Armor, Black PVC Outer Jacket, CSA HL SUN RES -40C

Availability
Global
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

6077 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeUPCOrder
6077 0103280Reel612825339410Order online
6077 0105000Reel612825339427Order online

Specifications

Product Overview

Suitable ApplicationsCEC Power and Control Applications

Construction Details

Overall Cable Diameter (Nominal)0.738 in

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Conductor(s)312 AWG7x20BC - Bare Copper
Ground Wire114 AWG7x22BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)XLP, XLPO, XLPE (Thermoset)0.030 in (0.76 mm)0.150 in (3.81 mm)Black, Red, Blue
Ground WireNo Insulation

Outer Shield

MaterialNo Shield

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.047 in (1.2 mm)
Nom. Diameter0.417 in (10.6 mm)
RipcordYes
ColorBlack

Armor

Armor Type & MaterialSIA - Steel Interlock Armor
Armor Thickness0.025 in (0.64 mm)
Diameter Over Armor0.642 in (16.3 mm)

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.048 in (1.2 mm)
Nom. Diameter0.738 in

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)1.65 Ohm/1000ft30 Amps per Conductor at 30oC
Ground Wire2.67 Ohm/1000ft (8.76 Ohm/km)

Voltage

Voltage Rating600 V (TECK 90)

Mechanical Characteristics

Max. Pull Tension515 lbs (234 kg)
Bulk Cable Weight406 lbs/1000ft

Temperature

UL Temperature90°C
Operating-40°C To +90°C

Bend Radius

Stationary Min.5.904 in (150.0 mm)
Installation Min.5.904 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance
CEC / C(UL) ComplianceTECK 90, HL.

History

Update and RevisionRevision Number: 0.54 Revision Date: 03-11-2026

Resources